195
Exchanging Data with the CPU Unit
Section 5-5
CJ1W-DA08V/08C
Note
For the CIO word addresses, n = CIO 2000 + unit number x 10.
Set Values and Stored Values
Allocation for Adjustment
Mode
For adjustment mode, set the operation mode switch on the front panel of the
Unit as shown in the following diagram. When the Unit is set for adjustment
mode, the ADJ indicator on the front panel of the Unit will flash.
(The CJ1W-DA08V/08C does not have this switch. Change the mode by set-
ting bits 00 to 07 in D(m+18) to C1 hex.)
I/O
Word
Bits
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Output
(CPU to
Unit)
n
Not used.
Conversion enable
---
Out-
put 8
Out-
put 7
Out-
put 6
Out-
put 5
Out-
put 4
Out-
put 3
Out-
put 2
Out-
put 1
n + 1
Output 1 set value
16
3
16
2
16
1
16
0
n + 2
Output 2 set value
n + 3
Output 3 set value
n + 4
Output 4 set value
n + 5
Output 5 set value
n + 6
Output 6 set value
n + 7
Output 7 set value
n + 8
Output 8 set value
Input
(Unit to
CPU)
n + 9
Alarm Flags
Output setting error
Out-
put 8
Out-
put 7
Out-
put 6
Out-
put 5
Out-
put 4
Out-
put 3
Out-
put 2
Out-
put 1
I/O
Item
Contents
Page
Output
Conversion enable
0: Conversion output stopped.
1: Conversion output begun.
Set value
16-bit binary data
Output setting error
0: No error
1: Output setting error
Common
Alarm Flags
Bits 00 to 03: Output setting error
Bits 04 to 07: Not used.
Bit 08:
Scaling data setting error
Bit 10:
Output hold setting error
Bit 11:
Not used.
Bit 12:
Conversion time/resolution or opera-
tion mode setting error
Bit 15:
Operating in adjustment mode
(Always 0 in normal mode.)
O
N
12
MODE
ON
OFF
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......