Origin Search and Origin Return Functions
Section 6-3
An origin search will not be started unless the origin search proximity speed is
less than the origin search high speed and unless the origin search/return ini-
tial speed is less than the origin search proximity speed.
6-3-3
Origin Search Error Processing
The CJ1M CPU Unit's pulse output function performs a basic error check
before starting to output pulses (when the instruction is executed) and will not
output pulses if the settings are incorrect. There are other errors that can
occur with the origin search function during pulse output, which may stop the
pulse output.
If an error occurs that stops pulse output, the pulse output's Output Stopped
Error Flag (A28007 or A28107) will be turned ON and the Pulse Output Stop
Error Code will be written to A444 or A445. Use these flags and error codes to
identify the cause of the error.
The Pulse Output Stop Errors will not affect the CPU Unit's operating status.
(The Pulse Output Stop Errors do not cause a fatal or non-fatal error in the
CPU Unit.)
Related Auxiliary Area Flags
Pulse Output Stop Error Codes
Word
Bits
Function
Read/Write
A280
07
Pulse output 0
Pulse Output Stopped Error Flag
0: No error
1: Stop error occurred
Read only
A281
07
Pulse output 1
Pulse Output Stopped Error Flag
0: No error
1: Stop error occurred
Read only
A444
00 to 15
Pulse output 0
Pulse Output 0 Stop Error Code (See table below.)
Read only
A445
00 to 15
Pulse output 1
Pulse Output 1 Stop Error Code (See table below.)
Read only
Error name
Error code
Likely cause
Corrective action
Operation after
error
CW Limit Stop Input
Signal
0100
Stopped due to a CW limit signal
input.
Move in the CCW direction.
Immediate stop,
No effect on
other port
CCW Limit Stop
Input Signal
0101
Stopped due to a CCW limit sig-
nal input.
Move in the CW direction.
No Origin Proximity
Input Signal
0200
The parameters indicate that the
Origin Proximity Input Signal is
being used, but a Origin Proxim-
ity Input Signal was not received
during the origin search.
Check the wiring of the Origin
Proximity Input Signal as well as
the PLC Setup's Origin Proxim-
ity Input Signal Type setting (NC
or NO) and execute the origin
search again. Turn the power
supply OFF and then ON if the
signal type setting was changed.
No effect on
other port
No Origin Input Sig-
nal
0201
The Origin Input Signal was not
received during the origin
search.
Check the wiring of the Origin
Input Signal as well as the PLC
Setup's Origin Input Signal Type
setting (NC or NO) and execute
the origin search again. Turn the
power supply OFF and then ON
if the signal type setting was
changed.
Summary of Contents for CJ1M-CPU21
Page 1: ...Cat No W395 E1 03 CJ series Built in I O CJ1M CPU21 22 23 CJ1M CPU Units...
Page 2: ...CJ series Built in I O CJ1M CPU21 22 23 CPU Units Operation Manual Revised August 2004...
Page 3: ...iv...
Page 19: ...xx...
Page 79: ...50 Wiring Examples Section 3 3...
Page 217: ...188 Origin Search and Origin Return Functions Section 6 3...
Page 220: ...191 Built in Outputs Section 7 1...
Page 247: ...218 Built in Outputs Section 7 1...
Page 251: ...222 Combinations of Pulse Control Instructions Appendix A...
Page 255: ...226 Using Pulse Instructions in other CPU Units Appendix B...
Page 263: ...234 Index...
Page 265: ...236 Revision History...