Conversion Instructions
Section 3-12
3-12-14 SIGNED BCD-TO-BINARY: BINS(470)
Purpose
Converts one word of signed BCD data to one word of signed binary data.
Ladder Symbol
Variations
Applicable Program Areas
Operands
C: Control Word
Specifies the signed BCD format. C must be 0000 to 0003.
Operand Specifications
C: Control word
S: Source word
D: Destination word
BINS(470)
C
S
D
Variations
Executed Each Cycle for ON Condition
BINS(470)
Executed Once for Upward Differentiation
@BINS(470)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Area
C
S
D
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
A448 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM
addresses in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM
addresses in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
#0000 to #0003
(binary)
---
Data Registers
DR0 to DR15