459
Conversion Instructions
Section 3-12
Flags
Example
When CIO 000000 is ON in the following example, LINE(063) copies bit 5
from D00100 to D00115 to the 16 bits in D00200.
3-12-13 LINE TO COLUMN: COLM(064)
Purpose
Converts the 16 bits of the source word to a column of bits in a 16-word range
of destination words (the same bit number in 16 consecutive words).
Ladder Symbol
Variations
Applicable Program Areas
Operands
D: First Destination Word
Specifies the first destination word. D and D+15 must be in the same data
area.
Name
Label
Operation
Error Flag
ER
ON if N is not within the specified range of 0000 to 000F.
OFF in all other cases.
Equals Flag
=
ON if D is 0000 after execution.
OFF in all other cases.
N: #0005
S:
D: D00200
to
to
&5
S: Source word
D: First destination word
N: Bit number
COLM(064)
S
D
N
Variations
Executed Each Cycle for ON Condition
COLM(064)
Executed Once for Upward Differentiation
@COLM(064)
Executed Once for Downward Differentiation Not supported
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...