175
Sequence Output Instructions
Section 3-4
Examples
Operation of DIFU(013)
When CIO 000000 goes from OFF to ON in the following example,
CIO 001000 is turned ON for one cycle.
Operation of DIFD(014)
When CIO 000000 goes from ON to OFF in the following example,
CIO 001000 is turned ON for one cycle.
3-4-5
SET and RESET: SET and RSET
Purpose
SET turns the operand bit ON when the execution condition is ON.
RSET turns the operand bit OFF when the execution condition is ON.
Ladder Symbols
Variations
Note Immediate refreshing is not supported by the CS1D CPU Units.
1 cycle
1 cycle
001000
1 cycle
1 cycle
001000
001000
B: Bit
SET
B
B: Bit
RSET
B
Variations
Executed Each Cycle for ON Condition
SET
Executed Once for Upward Differentiation
@SET
Executed Once for Downward Differentiation %SET
Immediate Refreshing Specification (See note.)
!SET
Combined
variations
Executed Once and Bit Refreshed
Immediately for Upward Differentiation (See
note.)
!@SET
Executed Once and Bit Refreshed
Immediately for Downward Differentiation
(See note.)
!%SET