166
Sequence Output Instructions
Section 3-4
In the following example, CIO 000001 is turned ON when CIO 000000 is ON
or bit 3 of D00010 is OFF.
3-4
Sequence Output Instructions
3-4-1
OUTPUT: OUT
Purpose
Outputs the result (execution condition) of the logical processing to the speci-
fied bit.
Ladder Symbol
Variations
Note Immediate refreshing is not supported by the CS1D CPU Units.
Applicable Program Areas
Operand Specifications
&3
Variations
Executed Each Cycle for ON Condition
OUT
Executed Once for Upward Differentiation
Not supported.
Executed Once for Downward Differentiation
Not supported.
Immediate Refreshing Specification (See note.)
!OUT
Block program areas
Step program areas
Subroutines
Interrupt tasks
Not allowed
OK
OK
OK
Area
OUT bit operand
CIO Area
CIO 000000 to CIO 614315
Work Area
W00000 to W51115
Holding Bit Area
H00000 to H51115
Auxiliary Bit Area
A44800 to A95915
Timer Area
---
Counter Area
---
TR Area
TR0 to TR15
DM Area
---
EM Area without bank
---
EM Area with bank
---
Indirect DM/EM
addresses in binary
---
Indirect DM/EM
addresses in BCD
---
Constants
---
Data Registers
---