8 Connecting the battery unit
8-1 Connecting the battery unit
BU150R
95
8
8 Connecting the battery unit
The backup time can be extended by connecting an optional expansion battery unit.
The following model is an expansion battery unit for this UPS.
Battery unit: BUM150RA
・
A maximum of 6 expansion battery units can be connected.
・
When one or more expansion battery units are connected, the charging time become
longer 24 hours per an expantion battery unit
・
For details on the backup time after expansion, see "4-1-4 Estimated backup time" ( P.63).
8-1 Connecting the battery unit
Caution (for connection)
To connect an expansion battery unit, pull out the UPS's power cable to
turn the power off.
After expansion, set the number of expansion battery units in the
operation mode settings (See "3-5 UPS operation mode settings" ( P.53)).
1.
Detach the battery expansion connector cover on the back of the UPS unit.
Loosen one screw at the bottom of the battery expansion cover when detaching.
①
②
Battery expansion connector cover