157
CompoNet Network Specifications
Section E-1
E-1-2
Communications Cables
Cable types
The following four types of cables can be used in a CompoNet network: round
cable I, round cable II, Flat Cable I and Flat Cable II.
Do not use other types of cables.
Recommended
CompoNet Cables
Cable type
Major applications
With or without a
communications
power supply
BDH
(signal
high)
BDL
(signal
low)
BS+
(positive side of
communications
power supply)
BS
−
(negative side of
communications
power supply )
Round cable I
(2-conductor
cable)
• Wiring
between the
Master
Board and a
Repeater
Unit,
• Wiring
between a
Repeater
Units and a
downstream
Slave Unit
• To wire with a commercially
available cable
• To supply power separately
from the communications
power
• Not to use a Bit Slave Unit
without
white
black
or blue
None
None
Round cable II
(4-conductor
cable)
• To wire with a commercially
available cable
• To use the communications
cable to supply the
communications power to
all Slave Units
with
white
green
or blue
red
black
Flat Cable I
(standard
cable)
• To use the communications
cable to supply the
communications power to
all Slave Units
• To use one or more Bit
Slave Units
with
white
blue
red
black
Flat Cable II
(sheathed
cable)
• To use the communications
cable to supply the
communications power to
all Slave Units
• To use one or more Bit
Slave Units
• To use in an environment
conforming to IP54; splash-
proof and drip-proof
with
white
blue
red
black
Model number
Specification
Available from
TCN-F1
Flat Cable I
SWCC Showa Cable Systems Co., Ltd.
TCN-F2
Flat Cable II
TCN-R1
Round Cable I
FCN-R1
Round Cable I
Fuji Electric Wire Industries Co., Ltd.
FCN-R2
Round Cable II
KOMP-F I
Flat Cable I
Kuramo Electric Co., Ltd.
KOMP-F II
Flat Cable II
KOMP-R I
Round Cable I
KOMP-R II
Round Cable II
Summary of Contents for 3G8F7-CRM21
Page 4: ...iv...
Page 10: ...x TABLE OF CONTENTS...
Page 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Page 74: ...54 Board Hardware Error Notification Section 4 8...
Page 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Page 230: ...210 Wiring for Power Supply Section E 5...
Page 234: ...214 Index...
Page 236: ...216 Revision History...
Page 237: ......