133
Shared Memory Area Specifications
Section B-3
B-3-8
Event Area in Detail
Event area (PC
→
BD)
This area is used when an explicit request message is sent by the PC to the
CompoNet Master Board or to a Slave or Repeater Unit.
Data format
Offset address: 0x3300
Detailed format
Definition of a node address with attributes
Offset
(Word)
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
+0
Byte length size after 1 (2 to 542)
+1
Reserved (0x00)
SID
+2
0x02
0x28
+3
Low of Node address with attributes
High of Node address with attributes
+4
Low of ServiceCode
High of ServiceCode
+5
Low of ClassID
High of ClassID
+6
Low InstanceID
High of InstanceID
+7
ServiceData[1]
ServiceData[0]
to
to
to
+272
ServiceData [531]
ServiceData [530]
Name
Access
Description
SID
Read/Write
The same value is added to the response of a
sent explicit message. It is used to identify to
which request the response pertains.
Set a certain value by the user application.
Settable range: 0x00 to 0xFF
Node address with
attributes
Read/Write
It specifies the destination node address with
attributes. See the following page for the node
address with attributes.
ServiceCode
Read/Write
It specifies the service code defined by the
explicit message.
Settable range: 0x0000 to 0x00FF
ClassID
Read/Write
It specifies the Class ID from which an explicit
message is requested.
Settable range: 0x0000 to 0x00FF
InstanceID
Read/Write
It specifies the Instance ID from which an explicit
message is requested.
Settable range: 0x0000 to 0x00FF
ServiceData
Read/Write
It specifies the data defined by a service code.
Number of effective bytes: 0 to 532 bytes
D15
D14
D13
D12
D11
D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
Type
0x0: Master Board
0x1: Normal IN or MIX Slave
0x2: Word OUT Slave
0x4: Bit IN or MIX Slave
0x5: Bit OUT Slave
0x7: Repeater
0
0
0
0
Master Board: Fixed to 0
Word Slave Unit: 0 to 0x3F
Bit Slave Unit: 0 to 0x7F
Repeater: 0 to 0x3F
Summary of Contents for 3G8F7-CRM21
Page 4: ...iv...
Page 10: ...x TABLE OF CONTENTS...
Page 46: ...26 Connecting the Communications Power Supply Cables Section 2 4...
Page 74: ...54 Board Hardware Error Notification Section 4 8...
Page 173: ...153 APPENDIX D Sample Program D 1 Sample Program 154...
Page 230: ...210 Wiring for Power Supply Section E 5...
Page 234: ...214 Index...
Page 236: ...216 Revision History...
Page 237: ......