2-7
2-2 Wiring
2
De
sign
Main Circuit Terminals
Control Circuit Terminal
Terminal symbol
Terminal name
Description
R/L1, S/L2,
T/L3
Main power supply input
terminal
Connect the input power supply.
U/T1,V/T2,
W/T3
Inverter output terminal
Connect to the 3-phase motor.
+1, P/+2
External DC reactor
terminal
Remove the short-circuit bar between terminals "+1" and
"P/+2", and connect the optional power factor
improvement DC reactor.
P/+2, RB
Braking resistor
connection terminals
Connect optional external braking resistors. (The RB
terminal is provided for the Inverters with 22 kW or lower
capacity.)
P/+2, N/-
Regenerative braking
unit connection terminal
Connect optional regenerative braking units.
G
Ground terminal
Inverter case ground terminal. Connect this terminal to the
ground.
type-D (200-V class), type-C (400-V class)
Terminal
symbol
Terminal name
Description
Specifications
An
alo
g
Frequ
ency reference in
put
FS
Frequency reference
power supply output
+10 V DC power supply for the FV terminal.
Allowable load current:
20 mA max.
FV
Frequency reference
input
(Voltage directive)
With a 0 to 10 V DC voltage input, the
frequency reaches the maximum at 10 V.
Set at A014 if the maximum frequency
needs to be achieved at lower than 10 V.
Input impedance 10 k
Ω
Allowable input voltage
range:
-0.3 to +12 V DC
FE
Auxiliary frequency
reference input
(Voltage directive)
With a 0 to ±10 V DC voltage input, the FE
signal is added to the frequency reference
signal of the FV or FI terminal. By changing
the setting, the frequency reference can be
input even with the FE terminal
independently.
Input impedance 10 k
Ω
Allowable input voltage
range:
0 to ±12 V DC
FI
Frequency reference
input
(Current directive)
With a 4 to 20 mA DC current input, the
maximum frequency is set at 20 mA. The FI
signal is only active when the AT terminal is
ON. Allocate the AT function to the multi-
function input terminal.
Input impedance 100
Ω
Allowable max. current:
24 mA
FC
Frequency reference
common
Common terminal for the frequency setting
signals (FV, FE and FI) and the analog
output terminals (AM and AMI). Do not
connect this terminal to the ground.
Continued to the next page
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......