4-117
4-2 Function Mode
4
Func
tions
High-torque Multi-operation
• When "sensorless vector control" or "0-Hz sensorless vector control" is selected with a single
Inverter, this function controls two motors of the same type to drive a single load.
• To use this function, you set the same parameters as when you select "Sensorless Vector Control"
(page 4-113) or "0-Hz Sensorless Vector Control" (page 4-114). However, set the motor
parameters as follows:
• Set motor parameters R1, R2, and L to one half of the set value for one motor.
• Set motor parameter Io to be twice the set value for one motor.
• Set motor parameter J to one half of the total moment of inertia of two motors and loads
connected to these motors.
• Select the motor capacity value closest to the total capacity of two motors.
• When different loads are driven with two motors, a fluctuation in one load affects the operating
condition of the other, which may hinder normal control.
To prevent this, be sure to operate a system in a way that the load driven by two motors is regarded
as one load.
Stabilization Parameter
• This function adjusts to reduce motor hunting.
• In case of motor hunting, check whether motor capacity H003/H203 and motor pole number
selection H004/H204 match your motor. If they do not, match them. If the motor's primary
resistance is smaller than that of the standard motor, increase the H006/H206/H306 set value
gradually. To run a motor with a capacity larger than the Inverter's rated capacity, reduce the set
value.
• Other than this function, the following methods are suggested to reduce hunting:
Lower the carrier frequency (b083). (Refer to page 4-65.)
Lower the output voltage gain (A045). (Refer to page 4-24.)
Related functions
A044/A244, F001, b040, b041 to b044, H002/H202, H003/H203, H004/
H204, H005/H205, H020/H220, H021/H221, H022/H222, H023/H223,
H024/H224, H050/H250, H051/H251, H052/H252
Parameter No.
Function name
Data
Default setting
Unit
H006/H206/H306
Stabilization parameter
0. to 255.:
If hunting occurs, adjust the set value.
100.
⎯
A045
Output voltage gain
20. to 100.:
If hunting occurs, reduce the set value.
100
%
b083
Carrier frequency
0.5 to 15.0:
If hunting occurs, reduce the set value.
5.0
kHz
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......