4-2 Function Mode
4
Functions
Motor Parameter Selection
• Set this parameter according to your motor.
• To use several motors with a single Inverter in the "VC", "special VP", or "free V/F setting" control
mode, calculate the total capacity of the motors and select the closest value in the motor capacity
selection.
• When automatic torque boost is used, improper setting of this parameter may result in torque
reduction or motor hunting.
• The motor parameters for "sensorless vector control", "0-Hz sensorless vector control", or "sensor
vector control" can be selected from the following three types:
• Motor parameter of a standard motor
• Motor parameter measured by offline auto-tuning
• Arbitrarily set motor parameter
• For 3rd control, motor parameters specified for 1st control are used.
*1. For 1st control A044, all items (00 to 05) are selectable. However, for 2nd control A244 and 3rd control A344,
the selectable range is 00 to 04, and 00 to 01, respectively.
Parameter No.
Function name
Data
Default setting
Unit
A044/A244/
A344
V/f characteristics
selection
00: Constant torque characteristics (VC)
01: Special reduced torque characteristics
(Special VP)
02: V/f free setting
*1
03: Sensorless vector control (SLV)
*1
04: 0-Hz sensorless vector control
*1
05: Sensor vector control (V2)
*1
00
⎯
H002/H202
Motor parameter
selection
00: Standard motor parameter
01: Auto-tuning parameter
02: Online auto-tuning parameter
00
⎯
H003/H203
Motor capacity
selection
0.2 to 160.0
Factory default
kW
H004/H204
Motor pole number
selection
2/4/6/8/10
4
Pole
H020/H220
Motor parameter R1
0.000 to 65.53
Depends on the
motor capacity.
Ω
H021/H221
Motor parameter R2
0.000 to 65.53
Depends on the
motor capacity.
Ω
H022/H222
Motor parameter L
0.00 to 655.3
Depends on the
motor capacity.
mH
H023/H223
Motor parameter Io
0.00 to 655.3
Depends on the
motor capacity.
A
H024/H224
Motor parameter J
0.001 to 9999. *
2
Depends on the
motor capacity.
kgm
2
H030/H230
Motor parameter R1
(auto-tuning data)
0.000 to 65.53
Depends on the
motor capacity.
Ω
H031/H231
Motor parameter R2
(auto-tuning data)
0.000 to 65.53
Depends on the
motor capacity.
Ω
H032/H232
Motor parameter L
(auto-tuning data)
0.00 to 655.3
Depends on the
motor capacity.
mH
H033/H233
Motor parameter Io
(auto-tuning data)
0.00 to 655.3
Depends on the
motor capacity.
A
H034/H234
Motor parameter J
(auto-tuning data)
0.001 to 9999.
Depends on the
motor capacity.
kgm
2
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......