4-107
4-2 Function Mode
4
Func
tions
MP Adjustment
• Adjust the Inverter output gain according to the meter connected to the MP terminal.
Analog Output AM/AMI Terminals
You can monitor the output frequency and current using the AM and AMI terminals on the control
circuit terminal block.
The AM terminal provides 0- to 10-V analog output.
The AMI terminal provides 4- to 20-mA analog output.
AM/AMI Selection
• Select a signal to output from the following table.
*1. This output is enabled only when "SLV", "0-Hz SLV", or "V2" is selected. (Refer to "Control Method (V/f
Characteristics)" (page 4-21).)
Parameter No.
Function name
Data
Default setting
Unit
C105
MP gain setting
50. to 200.: Set a gain for the MP monitor.
100.
%
Related functions
C027, b081
Parameter
No.
Function name
Data
Default
setting
Unit
C028/C029
AM selection
/
AMI selection
00: Output frequency (0 to Max. frequency (Hz)
*3
)
00
⎯
01: Output current (0% to 200%)
02: Output torque
*1
(0% to 200%)
04: Output voltage (0% to 100%)
05: Input voltage (0% to 200%)
06: Thermal load rate (0% to 100%)
07: LAD frequency (0 to Max. frequency [Hz])
09: Motor temperature (0
°
C to 200
°
C) (0
°
C output at 0
°
C or
lower)
10: Fin temperature
(0
°
C to 200
°
C) (0
°
C output at 0
°
C or lower)
11: Output torque (signed)
(AM output only. 0% to 200%
*1 *2
)
13: Not used
14: Not used
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......