4-103
4-2 Function Mode
4
Func
tions
Light Load Detection Signal
• This signal is output when output current falls below the light load detection level (C039).
• In light load signal output mode C038, you can set whether this output is enabled in any operation
mode, or only in constant speed operation.
Operation Ready Signal
• This signal is output when the Inverter becomes ready for operation (ready to receive the RUN
command).
• Even if the RUN command is input while this signal is not output, the Inverter does not recognize
the RUN command.
• If this signal is not output, check if the input power supply voltage (R, S, T) is within the specified
range.
Parameter No.
Function name
Data
Default setting
Unit
C021 to C025
Multi-function output
terminal selection
43: LOC (light load detection signal)
⎯
⎯
C026
Relay output (MA, MB)
function selection
05
C038
Light load signal output
mode
00: Enabled in operation
01: Enabled only in constant speed
operation
01
⎯
C039
Light load detection level
0.0 to 2.0 × Rated current:
Set an output level for low current signals.
Rated current
A
Output
current (A)
Low current
signal detection
level
(C039)
Low current signal
Parameter No.
Function name
Data
Default setting
Unit
C021 to C025
Multi-function output
terminal selection
50: IRDY (operation ready signal)
⎯
⎯
C026
Relay output (MA, MB)
function selection
05
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......