4-101
4-2 Function Mode
4
Func
tions
Network Error
• Enabled only when ModBus-RTU is selected for RS485 communication.
• If a reception timeout error occurs, this signal is output until reception of the next data.
• Set a time before reception timeout in communication error timeout C077.
• For details, refer to "4-4 Communication Function".
Cooling Fan Speed Drop Signal
• This signal is output when detecting that the Inverter's built-in cooling fan rotation speed is reduced
to 75% or less.
• If "01" is selected in cooling fan control b092, this signal is not output even while the fan is stopped.
• While this signal is output, check the cooling fan for clogging.
• Life assessment monitor d022 shows the status of this signal.
Parameter No.
Function name
Data
Default setting
Unit
C021 to C025
Multi-function output
terminal selection
32: NDc (network communication
disconnection detection)
⎯
⎯
C026
Relay output (MA, MB)
function selection
05
C077
Communication error
timeout
0.00 to 99.99:
Set a time before reception timeout.
0.00
s
External controller
Inverter
Monitor timer
Communication trip time
(C077)
Communication disconnection detection signal (NDc)
Parameter No.
Function name
Data
Default setting
Unit
C021 to C025
Multi-function output terminal
selection
40: WAF
(cooling fan life warning signal)
⎯
⎯
C026
Relay output (MA, MB)
function selection
05
Related functions
b092, d022
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......