4-80
4-2 Function Mode
4
Functions
2nd/3rd Control Function
• You can switch between three motors to control the Inverter by allocating 08 (SET)/17 (SET3) to
any of multi-function inputs 1 to 8 (C001 to C008) and then turning on/off the SET/SET3 terminal.
Parameter No.
Function name
Data
Default setting
Unit
C001
Multi-function input 1
selection *
1
01: RV (reverse)
02: CF1 (multi-step speed setting binary 1)
03: CF2 (multi-step speed setting binary 2)
04: CF3 (multi-step speed setting binary 3)
05: CF4 (multi-step speed setting binary 4)
06: JG (jogging)
07: DB (external DC injection braking)
08: SET (2nd control)
09: 2CH (2-step acceleration/deceleration)
11: FRS (free-run stop)
12: EXT (external trip)
13: USP (USP function)
14: CS (commercial switching)
15: SFT (soft lock)
16: AT (analog input switching)
17: SET3 (3rd control)
18: RS (reset)
20: STA (3-wire start)
21: STP (3-wire stop)
22: F/R (3-wire forward/reverse)
23: PID (PID enabled/disabled)
24: PIDC (PID integral reset)
26: CAS (control gain switching)
27: UP (UP/DWN function accelerated)
28: DWN (UP/DWN function decelerated)
29: UDC (UP/DWN function data clear)
31: OPE (forced operator)
32: SF1 (multi-step speed setting bit 1)
33: SF2 (multi-step speed setting bit 2)
34: SF3 (multi-step speed setting bit 3)
35: SF4 (multi-step speed setting bit 4)
36: SF5 (multi-step speed setting bit 5)
37: SF6 (multi-step speed setting bit 6)
38: SF7 (multi-step speed setting bit 7)
39: OLR (overload limit switching)
40: TL (torque limit enabled)
41: TRQ1 (torque limit switching 1)
42: TRQ2 (torque limit switching 2)
43: PPI (P/PI switching)
44: BOK (brake confirmation)
45: ORT (orientation)
46: LAC (LAD cancel)
47: PCLR (position deviation clear)
48: STAT (pulse train position command input permission)
50: ADD (frequency addition)
51: F-TM (forced terminal)
52: ATR (torque command input permission)
53: KHC (integrated power clear)
54: SON (servo ON)
55: FOC (preliminary excitation)
56: Not used
57: Not used
58: Not used
59: Not used
60: Not used
61: Not used
62: Not used
63: Not used
65: AHD (analog command held)
66: CP1 (position command selection 1)
67: CP2 (position command selection 2)
68: CP3 (position command selection 3)
69: ORL (zero return limit signal)
70: ORG (zero return startup signal)
71: FOT (forward driving stop)
72: ROT (reverse driving stop)
73: SPD (speed/position switching)
74: PCNT (pulse counter)
75: PCC (pulse counter clear)
no: NO (no allocation)
01
⎯
C002
Multi-function input 2
selection
18
C003
Multi-function input 3
selection *
1
12
C004
Multi-function input 4
selection
02
C005
Multi-function input 5
selection
03
C006
Multi-function input 6
selection
04
C007
Multi-function input 7
selection
05
C008
Multi-function input 8
selection
06
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......