4-71
4-2 Function Mode
4
Func
tions
Automatic Carrier Frequency Reduction Function
• This function automatically reduces carrier frequency according to an increase in output current.
• This function is enabled when automatic carrier frequency reduction selection b089 is set to "01".
• When output current exceeds 60%, 72%, 84% and 96% of the rated current, the carrier frequency
is reduced to 12, 9, 6, and 3 kHz, respectively.
When the output current falls below -5% of each level, this function will be reset.
• The carrier frequency reduction rate is 2 kHz per second.
• The upper limit of carrier frequency variable with this function conforms to the set value of carrier
frequency b083, and the lower limit is 3 kHz.
Note: When b083 is 3 kHz or lower, this function is disabled regardless of the b089 setting.
Parameter No.
Function name
Data
Default setting
Unit
b089
Automatic carrier reduction
00: Disabled
01: Enabled
00
⎯
Carrier frequency reduction starting level
(Recovery level)
Reduced carrier frequency (kHz)
Less than 60% of the rated current
15.0
60% (55%) of the rated current
12.0
72% (67%) of the rated current
9.0
84% (79%) of the rated current
6.0
96% (91%) of the rated current
3.0
15.0 kHz
60%
Output current (%)
Carrier
frequency
12.0 kHz
9.0 kHz
6.0 kHz
3.0 kHz
72% 84% 96%
0
100
50
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......