4-66
4-2 Function Mode
4
Functions
• If the above maximum rated carrier frequency and the derating value at 15 kHz are exceeded, the
Inverter may be damaged and/or the service life may be shortened.
Parameter Initialization
• You can initialize the rewritten set values and reset to the factory default.
• You can clear trip data.
• You cannot clear the P100 to P131 set values, RUN time, or power ON time.
5.5 kW
15
100%
15
100%
7.5 kW
15
100%
15
100%
11 kW
12
90% (41.4 max.)
15
100%
15 kW
12
95% (60.8 A max.)
14
95% (30.4 A max.)
18.5 kW
10
90% (68.4 A max.)
10
90% (34.2 A max.)
22 kW
7
70% (66.5 A max.)
6
75% (36.0 A max.)
30 kW
5
80% (96.8 A max.)
10
75% (43.5 A max.)
37 kW
10
75% (108.7 A max.)
8
80% (60.0 A max.)
45 kW
5
70% (127.4 A max.)
9
75% (68.2 A max.)
55 kW
5
70% (154 A max.)
6
60% (67.2 A max.)
75 kW
⎯
⎯
6
85% (126.7 A max.)
90 kW
⎯
⎯
4
75% (132.0 A max.)
110 kW
⎯
⎯
6
70% (151.9 A max.)
132 kW
⎯
⎯
3
60% (156.0 A max.)
Voltage
200-V class
400-V class
Capacity
Max. fc (kHz)
Derating at fc = 15 kHz
Max. fc (kHz)
Derating at fc = 15 kHz
(75 to 132 kW is for 10 kHz)
60
55
100
95
90
85
80
75
70
65
0.5 2
4
6
8
10
12
15
14
60
55
100
95
90
85
80
75
70
65
0.5 2
4
6
8
10
12
15
14
200-V class
400-V class
Output current der
ating
Carrier frequency (kHz)
Output current der
ating
Carrier frequency (kHz)
15 kW
37 kW
30 kW
11 kW
18.5 kW
22 kW
45, 55 kW
15 kW
22 kW
132 kW
110 kW
18.5 kW
37 kW
55 kW
30 kW
45 kW
75 kW
90 kW
Parameter No.
Function name
Data
Default setting
Unit
b084
Initialization selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes
data
00
⎯
b085
Initialization parameter
selection
00: Do not change
00
⎯
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......