Operation Frequency Function
• Two systems of frequency reference operation results are available for the frequency reference
and PID feedback value.
Note 1: When this function is enabled, the Up/Down function cannot be used. In addition, frequency cannot be
changed through key operations from output frequency monitor d001, frequency conversion monitor
d007, or output frequency setting F001.
Note 2: The same setting is available in A141 and A142.
• To use this function as a frequency reference, set frequency reference selection A001 to "10".
• To use this function as a PID feedback, set PID feedback selection A076 to "10".
Frequency Addition Function
• The value set in frequency addition amount A145 can be added to or subtracted from the selected
frequency reference value.
• To use this function, allocate 50 (ADD) to any of the multi-function inputs.
The A145 value is added or subtracted with the ADD terminal turned on.
Note 1: If the sign of the frequency reference is changed ((-)
→
(+), or (+)
→
(-)) as a result of operation, the
rotation direction will be inverted.
Note 2: When the PID function is used, the frequency addition function is enabled for a PID target value.
(Note that A145 is displayed in % (in increments of 0.01%).)
Parameter No.
Function name
Data
Default setting
Unit
A141
Operation frequency
input A setting
00: Digital Operator (F001)
(A020/A220/A320)
01: Digital Operator (FREQ adjuster)
(Enabled when 3G3AX-OP01 is
used.)
02: Input FV
03: Input FI
04: RS485 communication
05: Option 1
06: Option 2
07: Pulse train frequency
02
⎯
A142
Operation frequency
input B setting
03
⎯
A143
Operator selection
00: Addition (A + B)
01: Subtraction (A - B)
02: Multiplication (A × B)
00
⎯
Related functions
A001 = 10, A076 = 10
Parameter No.
Function name
Data
Default setting
Unit
A145
Frequency addition
amount
0.0 to 400.0
0.00
Hz
A146
Frequency addition
direction
00: Add A145 value to output frequency
01: Subtract A145 value from output
frequency
00
⎯
Related functions
C001 to C008, ADD input
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......