background image

AWAG Elektrotechnik AG   Sandbüelstrasse 2   CH-8604 Volketswil 

1510000.docx / 1876064 

Tel. +41 44 908 19 19  Fax +41 44 908 19 99  [email protected]  www.awag.ch 

SW: TST_V190404 / 15.04.2019 Seite 1 / 6 

TST230/10 

Bedienungsanleitung  

Manual 

UP-Tasterschnittstelle 

flush mounted push-button 

2-Kanal 

interface 2-channel 

 

Bezeichnung 

Typ / Type 

Art.-No./Item N°  Designation 

UP-Tasterschnittstelle 2-Kanal 

2 Eingänge potentialfrei, Versorgungsspannung 230 V~ 

TST230/10 

1510 000 

Flush mounted push-button interface 2-channels  

2 inputs potential free, supply voltage 230 V~ 

 
KURZANLEITUNG 

  Tasterschnittstelle gemäss Schema anschliessen 

  Eingangsmodus wählen (Taster oder Schalter) 

  Eingang Auswertung wählen (Wippe, Taste, 

Schaltuhr, Wetterstation) 

  Drehschalter HEX auf 0 stellen 

 

BRIEF  INSTRUCTION  

  Attach push-button interface according to 

schematic 

  Choose input mode (button or switch) 

  Choose input evaluation (rocker, push-button, 

time switch, weather station) 

  Turn the rotary switch HEX to 0 

 

EIGENSCHAFTEN 

  2 potentialfreie Eingänge für drahtgebundene 

Sensoren 

  Auswertung der Eingänge als Wippe, Taste, 

Schaltuhr oder Wetterstation 

  1…5 Sende-Wiederholungen 

  Klonfunktion 

  Senden auf Chip ID oder Basis ID 

  Splitfunktion für Omnio Funktaster 

  Repeaterfunktion 

  EnOcean Equipment Profile (EEP) F6-02-01 

 

ARCO fähig (AWAG Remote Commissioning) 

FEATURES 

  2 potential free inputs for wired sensors 

  Input evaluation as rocker, push-button, time 

switch or weather station 

  1…5 retransmissions 

  Clone function 

  Send on chip ID or Base ID 

  Split function for Omnio radio transmitters 

  Repeater function 

  EnOcean Equipment Profile (EEP) F6-02-01  

 

ARCO ready (AWAG Remote Commissioning)

ALLGEMEIN 

Die Omnio Aktoren (Empfänger) werden über Funksignale der Omnio Sender an-

gesteuert. Jeder Sender kann eine unbegrenzte Anzahl von Aktoren ansteuern. Die 

Funksender werden manuell durch ein einfaches Verfahren auf den Aktor ein- und 

ausgelernt. Jedem Sender können am Aktor eine Funktion und verschieden-ste Pa-

rameter zugeordnet werden. 

 

Mit ARCO-Technologie lassen sich alle Omnio Aktoren vollständig und ohne ma-

nuellen Zugriff zum Gerät per Funk konfigurieren. Die leistungsstarke Software E-

Tool bildet dabei das Herzstück, um Projekte beliebiger Grösse bequem am 

Schreibtisch zu planen, konfigurieren und dokumentieren. 

 

PRODUKTBESCHREIBUNG 

Die Omnio UP-Tasterschnittstelle 2-Kanal TST230/10 ist eine Binäreingabeeinheit 

zur Einbindung von drahtgebundenen Schaltern, Tastern und Sensoren in das Om-

nio Funkbussystem. An seine Eingänge können zwei potentialfreie Schliesskon-

takte angeschlossen werden. In Abhängigkeit der gewählten Auswertungsart 

(Wippe, Taste, Schaltuhr oder Wetterstation) sendet die Tasterschnittstelle bei Be-

tätigung der Schliesskontakte IN1 und IN2 die entsprechenden Funktelegramme, 

welche sich wiederholen und zusätzlich auch vervielfachen (klonen) lassen. Unab-

hängig davon kann man Omnio Funktaster einlernen und deren Telegramme über 

die Splitfunktion vervielfachen.  Bidirektionale Kommunikation,  EEP  F6-02-01, 

ARCO fähig (AWAG Remote Commissioning). Zusätzlich kann bei Reichweiten-

problemen die eingebaute Repeaterfunktion aktiviert werden. Geeignet für die Un-

ter- oder Aufputzmontage in Kunststoffdosen. 

 

 

GENERAL 

The Omnio actuators (receivers) are controlled by radio signals coming from the 

Omnio transmitters. Each transmitter is able to control an unlimited number of ac-

tuators. The radio transmitter can be manually programmed and deprogrammed to 

an actuator by following a simple procedure. Via actuator each transmitter can be 

given a certain function and different parameters.  

 

With ARCO technology, all Omnio actuators can be configured completely by radio 

without manual access to the device. The powerful software E-Tool constitutes the 

key component for convenient planning, configuring and documenting projects of 

any size right at your desk. 

 

PRODUCT DESCRIPTION   

The Omnio flush mounted push-button interface 2-channels TST230/10 is a binary 

input device to integrate wired push-buttons, switches and sensors into the Omnio 

radio system. Two potential free closing contacts may be connected to its inputs. 

Depending on the chosen type of evaluation (rocker, push-button, time switch or 

weather station) the push-button interface transmits, repeats and additionally mul-

tiplies the matching radio telegram by actuating the closing contacts IN1 and IN2. 

Apart from that Omnio radio transmitters can be programmed and their radio tele-

gram can be multiplied via split function. Bidirectional communication, EEP F6-02-

01, ARCO ready (AWAG Remote Commissioning). In addition, this actuator can be 

used as repeater in case of range issues. Suitable for flush mounted sockets. 

ANZEIGE- UND BEDIENELEMENTE 

 

Klemmen 

  L 

Netzspannung L 110 – 240 V~ 

  N 

Netzspannung N 110 – 240 V~ 

  IN1 

Eingang 1 

  IN2 

Eingang 2 

  OUT 

Gemeinsamer Ausgang 

 

 

Bedienelemente 

  CLR 

Taste und LED Clear 

  LRN 

Taste und LED Learn 

  HEX 

Drehschalter 0..15 

DISPLAY AND OPERATING ELEMENTS 

 

Terminals  

  L 

line voltage L 110 – 240 V~ 

  N 

line voltage N 110 – 240 V~ 

  IN1 

input 1 

  IN2 

input 2 

  OUT 

common output 

 

 

Operating eleme

nts 

  CLR 

button and LED clear 

  LRN 

button and LED learn 

  HEX 

rotary switch 0..15 

 

 

 

 

EnOcean-Technologie (868 MHz) 

Summary of Contents for TST230/10

Page 1: ... Eingänge können zwei potentialfreie Schliesskon takte angeschlossen werden In Abhängigkeit der gewählten Auswertungsart Wippe Taste Schaltuhr oder Wetterstation sendet die Tasterschnittstelle bei Be tätigung der Schliesskontakte IN1 und IN2 die entsprechenden Funktelegramme welche sich wiederholen und zusätzlich auch vervielfachen klonen lassen Unab hängig davon kann man Omnio Funktaster einlerne...

Page 2: ...eter ist in Tabelle 4 GERÄTEPARAMETER zu finden 1 Geräteparameter wählen 2 Drehschalter gemäss Tabelle 4 Spalte 1 einstellen 3 Einlernmodus durch einen langen Tastendruck 2 s auf aktivieren LRN leuchtet und CLR blinkt 4 Drehschalter gemäss Tabelle 4 Spalte 3 einstellen 5 drücken LRN und CLR erlöschen INSTALLATION This device is suitable for flush mounted sockets installed indoors dry rooms through...

Page 3: ...en Taste I Ausgang Kanal 2 freischalten 2 Button O Lock output channel 2 Button I Unlock output channel 2 Taste O Ausgang Kanal 1 und 2 sperren Taste I Ausgang Kanal 1 und 2 freischalten 11 Button O Lock output channel 1 and 2 Button I Unlock output channel 1 and 2 ARCO FUNKTIONEN ARCO FUNCTIONS X03 Wippe splitten Wippe dreimal splitten bei Tastendruck Base ID Offset 1 Kanäle A B C 0 2 s drücken p...

Page 4: ... 2 s 15 LRN Taste 2 s drücken press LRN button 2 s Reset to factory settings Attention The programmed transmitters remain Beispiele Examples Wippe beidseitig löschen 0 CLR 2 s drücken Wippentaste O 2x drücken Wippentaste I 2x drücken CLR Delete both sides of a rocker 0 press CLR 2 s press button O 2x press button I 2x CLR Taste löschen 0 CLR 2 s drücken Taste 2x drücken CLR Delete push button 0 pr...

Page 5: ...ived radiograms and retransmit them Only one device must be activated as a repeater within a radius of 5 meters Aus 15 2 s drücken press 2 s 0 drücken press Off Level 1 Verstärkt nur Originaltelegramme 1 Level 1 Amplifies original radio telegrams Level 2 Verstärkt Originaltelegramme und bereits einmal verstärkte Tele gramme 2 Level 2 Amplifies original radio telegrams and also retransmitted radio ...

Page 6: ...crew terminals Schutzart IP20 Protection class Überspannungsschutz Overvoltage protection Dauerkurzschlussfest Steuerteil Permanent short circuit proof control unit Technologie EnOcean 868 MHz Technology Funkmodul EnOcean TCM320 bidirektional bidirectional Radio module EnOcean Equimpent Profile EEP F6 02 01 EnOcean Equipment Profile EEP Umweltbedingungen 20 40 C 5 90 rH non condensing Environment ...