Generac PowerZone Modbus TCP
Configuration Guide
IM-815-02
04-MAR-2020
The OmniMetrix (OMNI) TrueGuard PRO monitor, with Modbus TCP functionality,
comes with default network configurations, and since it is easy to configure the
network settings on the PowerZone (PZ) control in the field, please configure the PZ
as follows:
The OMNI unit is configured for these network values:
IP Address: 10.0.1.202
Subnet Mask: 255.255.0.0
Gateway: 10.0.1.1
For a
single
PZ control, set the following:
Modbus Slave ID = 1
IP Address: 10.0.1.101
Subnet Mask: 255.255.0.0
Gateway: 10.0.1.1 (this is not important)
If
multiple
PZ controls are to be connected, such as in an MPS
configuration, use the following:
MPS Gen #
Modbus Slave ID IP Address
Subnet Mask
1
1
10.0.1.101
255.255.0.0
2
2
10.0.1.102
255.255.0.0
3
3
10.0.1.103
255.255.0.0
4
4
10.0.1.104
255.255.0.0
5
5
10.0.1.105
255.255.0.0
6
6
10.0.1.106
255.255.0.0
7
7
10.0.1.107
255.255.0.0
8
8
10.0.1.108
255.255.0.0