Omniflex Omni8m C1477B Series User Manual Download Page 14

 

 

C1477B User Manual (UMC1477BR04) 

- 14 - 

Copyright Omniflex 

 

6.  OPERATION 

6.1  Power-up 

When power is applied to the Omni8

, the unit commences an automatic, built-in circuit test 

routine. This results in the unit sounding the audible for approximately half a second followed by 
the cyclic illumination of each lamp in turn from 1 to 8 and back to 1 again etc. i

n a “marching 

sequence”. 
If no internal faults are detected in the unit, then this test mode display continues until the 
Acknowledge Pushbutton is pressed or until an input enters the alarm state. 

If a fault was detected, then the unit will display a fault indication by continuously flashing one of 
the lamps. If this occurs, then the unit must be sent for service. 

If a new alarm occurs while the Omni8

 is in this test routine, the unit will immediately revert to 

its normal mode of operation and will deal with the alarm state according to the pre-selected 
alarm sequence. 

6.2  Normal Operation 

During the normal operation, the Omni8

 will act upon any alarm states according to its pre-set 

alarm sequences.  (The instructions for setting-up these sequences are given in SECTION 3.3). 

Section 8 provides detailed block diagrams for the function of each alarm sequence. 

When an alarm condition occurs and the horn sounds, the operator should depress the relevant 
pushbuttons, where necessary, according to the pre-selected alarm sequence. 

When the Omni8

 is put into its test routine by depressing the TEST pushbutton, any existing 

alarm states are “remembered” and the alarm annunciator will revert to its previous state when it 
returns to its normal mode of operation. 

If a new alarm state occurs while the Omni8

 is performing its test routine, the unit will 

immediately revert to its normal mode of operation and deal with the alarm state according to 
the pre-selected alarm sequence. 

6.3  Test Functions 

6.3.1 

Overview of the Test Functions 

The Test button operates as a combined lamp test and circuit test function. 

No information is lost during the entire test routine, and each alarm display returns to the 
exact state it was in before the test. 

6.3.2 

Pressing the Test Button 

When the Test button is pressed, the unit checks the results of its regular full circuit test, 
and if all checks performed pass, then a normal lamp test is performed by illuminating all 
of the lamps while the Lamp Test Pushbutton is held down. 

If the ci

rcuit Test fails then the unit enters its “marching sequence” test routine described in 

Section  6.3.5  and  the  test  failure  code  will  be  displayed  by  flashing  one  of  the  lamps 
continuously. 

In  this  way,  the  display/annunciator  Test  button  acts  both  as  a  Lamp  Test  and  Circuit 
Function. 

6.3.3 

Fault Indication on Circuit Test 

If a fault is found in one of the tests performed, then the unit enters its full “marching lamp 
sequence”, with, in addition, one or more of the lamps flashing continuously to indicate the 
fault located. This is described in detail in Section 6.3.5 

Summary of Contents for Omni8m C1477B Series

Page 1: ...Omni8 Alarm Annunciator C1477B x...

Page 2: ...in any form or by any means electronically photocopying mechanical or otherwise nor its contents disclosed either wholly or in part without the consent in writing of or in accordance with the conditi...

Page 3: ...m annunciator systems Available in a range of power supply options the rugged Omni8 is designed to fit directly into local electrical panels without the need for external power conditioning or interfa...

Page 4: ...ATION 11 3 1 Installing the Omni8 in a panel 11 4 ELECTRICAL INSTALLATION 12 4 1 Introduction 12 4 2 Connection Table 12 4 3 Connecting the alarm inputs 12 4 4 Connecting the Relay 13 4 5 Connecting t...

Page 5: ...nt monitoring Integral audible device and control pushbuttons for ease of installation and use Relay output for common group alarm or external audible device control Removable terminals for easy insta...

Page 6: ...ction Figure 1 3 Side View showing 8 way Set up Switches 1 5 Installation and Set up Procedure The following steps should be implemented in the order shown to configure and install an Omni8 alarm annu...

Page 7: ...witch of SW2 e g SW2 1 sets the contact sense for input 1 and SW2 8 sets the contact sense for input 8 When the switch is OFF up then the input is set to NORMALLY OPEN i e the input will enter the ala...

Page 8: ...12 0 0 1 1 0 MOMENTARY ALARM AUTO RESET TIME DELAY ON RETURN TO NORMAL 16 60 seconds 13 1 0 1 1 0 PULSE MONITORING ALARM MANUAL RESET 17 17 1 1 1 1 0 INPUTS 1 4 SEQUENCE 1 INPUTS 5 8 SEQUENCE 27 FOR...

Page 9: ...d normally by pressing the Silence or Acknowledge Pushbutton This is useful in environments where the local internal audible will not be heard 4 Relay acts in Multiple Reflash Mode The relay is normal...

Page 10: ...C1477B User Manual UMC1477BR04 10 Copyright Omniflex...

Page 11: ...CKNESS 8mm MAXIMUM PANEL 42 44 92 180 48 Location of DIP switches Mounting bracket Figure 3 1 Mounting an Omni8 3 1 Installing the Omni8 in a panel Remove the metal bracket from the unit by removing t...

Page 12: ...wetting 10 Relay Change over Contact Normally Open Connection 11 Relay Change over Contact Common Connection 12 Relay Change over Contact Normally Closed Connection 13 No Connection 14 Earth 15 dc Pow...

Page 13: ...ported by all operating systems There is also a README TXT file on this disk Run this first to see which version of program you must run to use the supplied templates 5 2 Creating the Legend Film To c...

Page 14: ...sequence When the Omni8 is put into its test routine by depressing the TEST pushbutton any existing alarm states are remembered and the alarm annunciator will revert to its previous state when it ret...

Page 15: ...this procedure of marching sequence followed by the brief blank display period will be repeated continuously until the ACKNOWLEDGE pushbutton is depressed or until an input changes state This marchin...

Page 16: ...C selectable by DIP switch Max open cct voltage 15V dc between Common positive and all input terminals Max closed cct current 2 mA per input Max loop resistance to detect closed circuit 200 ohms Min...

Page 17: ...haracters 2 5mm Fast Flash Rate 140 flashes per minute Slow Flash Rate 35 flashes per minute TEMPERATURE RANGE Operating Relative Humidity 0 C to 60 C 32 F to 140 F Up to 90 RH non condensing Storage...

Page 18: ...nts IEC 61000 4 4 1995 2 kV DC power port 1 kV input output lines Supply Variations IEC 61000 4 7 1991 24 V dc 15 10 RoHS Compliance 2011 65 EU RoHS2 ORDERING INFORMATION C1477B 1 Omni8 with PSU 10 15...

Page 19: ...P ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 LAMP OFF HORN OFF HORN OFF Sequence 2 Momentary Fleeting Alarm Manual Reset Timer option off STATE 4 STATE 3 RESET WHILE NORMAL ABNORMAL LAMP ON...

Page 20: ...Only No Lock in Auto Reset Timer option off STATE 4 STATE 3 RETURN TO NORMAL ABNORMAL LAMP ON HORN OFF 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 2 STATE 1 LAMP OFF HORN OFF SIL ACK LAMP FAST FL...

Page 21: ...RETURN TO NORMAL ABNORMAL ACK WHILE NORMAL Sequence 4 Momentary Fleeting Alarm Manual Reset with Ringback Timer Delay on inputs RESET ABNORMAL 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE...

Page 22: ...FAST FLASH HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL Sequence 5 Momentary Fleeting Alarm First Out Manual Reset Auto Reset on subsequent Alarms RETURN TO NORMAL ABNORMAL S...

Page 23: ...TIVE FIRST OUT INACTIVE FIRST OUT INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL ACK ACK WHILE ABNORMAL LAMP SLOW FLASH FIRST OUT ACTIVE LAMP ON LAMP ON LAMP FAST FLAS...

Page 24: ...et Re alarm after time out if still abnormal RESET WHILE NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH H...

Page 25: ...TIMER RUNNING TIME OUT LAMP FAST FLASH HORN ON TIMER OFF SIL LAMP FAST FLASH HORN OFF TIMER OFF ACK HORN OFF TIMER OFF T ACK LAMP SLOW FLASH Sequence 12 Momentary Fleeting Alarm Auto Reset with Time D...

Page 26: ...TIMER OFF TIMER OFF LAMP OFF HORN OFF TIMER OFF TIMER OFF ABNORMAL RETURN TO NORMAL ABNORMAL RETURN TO NORMAL TIME OUT TIME OUT ACK WHILE ABNORMAL SIL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NOR...

Page 27: ...L LAMP ON Sequence 21 Momentary Fleeting Alarm First Out Multiple Groups Auto Reset RETURN TO NORMAL ABNORMAL SUBSEQUENT 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN OFF SI...

Page 28: ...INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RETURN TO NORMAL ACK WHILE NORMAL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NORMAL LAMP ON LAMP ON LAMP FAST FLASH LAMP FAST FLASH LAM...

Page 29: ...larm after time out if still abnormal RETURN TO NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH HORN ON SI...

Page 30: ...OFF ACK HORN OFF TIMER OFF T ACK WHILE ABNORMAL LAMP SLOW FLASH ACK WHILE NORMAL Sequence 29 Pulse Monitoring Alarm Auto Reset 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN...

Reviews: