KURZ AN LE I TUNG  

  Thermostataktor gemäss Schema anschliessen 

  Drehschalter HEX auf 0 stellen 

  LRN 2 Sekunden drücken 

  Durch weiteres Drücken auf LRN den Kanal wählen. Die 

Kanalnummer erscheint auf der 7-Segment-Anzeige 
SEG. 

  LRN-Taste des Raumfühlers in der Nähe des 

Thermostataktors betätigen. CLR leuchtet während einer 
Sekunde, danach ist der Sender eingelernt 

  Zum Beenden CLR drücken 

FUNK TI ONE N  

  Temperaturregelung in Einzelräumen durch 2-Punkt-

Regler mit einstellbarer Hysterese 

  Geeignet für Omnio Raumfühler RTF 

  Sollwertvorgabe auch über EEP möglich 

  Vordefinierte Betriebsarten, z.B. Nachtabsenkung 

  Automatische Frostschutzfunktion bei 8 °C 

  Umschaltung auf zweiten Sollwert mit Omnio Wand-

sender oder Key-Card Schalter 

  Fenster- und Schiebetürüberwachung 

  Repeaterfunktion 

  EnOcean Equipment Profile (EEP) D2-34-02 

 

ARCO fähig (AWAG Remote Commissioning) 

BRI E F  I NS TR UC TI ON    

  Attach thermostat actuator according to schematic 

  Turn the rotary switch HEX to 0 

  Press LRN 2 seconds 

  Repress LRN to increment the channel number. The 

channel  appears on the 7-segment display SEG. 

  Press LRN-button of indoor sensor while keeping it close 

to the actuator. CLR lights up for a second, after that the 
transmitter is programmed  

  To finish press CLR 

 

FUNC TI ONS  

  Temperature control in individual rooms by 2-point 

controller with adjustable hysteresis 

  Suitable for Omnio RTF room sensors 

  Setpoint via EEP possible 

  Predefined modes, e.g. night mode 

  Automatic frost protection at 8 °C 

  Setpoint switchover with Omnio transmitter or key-card 

switch 

  Window and sliding door surveillance 

Repeater function 

  EnOcean Equipment Profile (EEP) D2-34-02 

 

ARCO ready (AWAG Remote Commissioning) 

AL LGE M E I N  

Die Omnio Aktoren (Empfänger) werden über Funksignale der Omnio Sender  an-
gesteuert. Jeder Sender kann eine unbegrenzte Anzahl von Aktoren ansteuern. Die 
Funksender werden manuell durch ein einfaches Verfahren auf den Aktor ein- und 
ausgelernt. Jedem Sender können am Aktor eine Funktion und verschiedenste Pa-
rameter zugeordnet werden. 
 
Mit ARCO-Technologie lassen sich alle Omnio Aktoren vollständig und ohne ma-
nuellen Zugriff zum Gerät per Funk konfigurieren. Die leistungsstarke Software E-
Tool  bildet  dabei  das  Herzstück,  um  Projekte  beliebiger  Grösse  bequem  am 
Schreibtisch zu planen, konfigurieren und dokumentieren. 

P RODUK TBE S CHRE I B UNG  

Der Omnio REG-Multi-Thermostataktor 8-Kanal REGH12/08 ist ein Gerät zum Re-
geln  von  Stellventilen  in  Bodenheizungen  oder  ähnlichen  elektrischen  Verbrau-
chern durch eine 2-Punkt-Regelung mit Hysterese. Seine acht potentialfreien Aus-
gänge können von je einem Omnio Raumfühler RTF und bis zu 8 Omnio Fenster-
kontakten oder -griffen in UND-Verknüpfung angesteuert werden. Der Raumfühler 
sendet Temperatur und Sollwert per Funk an den Thermostataktor. Die gewünschte 
Raumtemperatur  lässt  sich  am  Raumfühler  über  die  Bedientasten  einstellen,  sie 
kann aber auch von einem übergeordneten System vorgegeben werden. Über Om-
nio Funksender sind verschiedene Betriebsmodi wie z.B. eine Nachtabsenkung an-
wählbar. Fällt die Temperatur unter 8 °C oder ist der Raumfühler defekt, wird auto-
matisch die Frostschutzfunktion aktiviert.  Bidirektionale Kommunikation, EEP  D2-
34-02, ARCO fähig  (AWAG Remote Commissioning). Zusätzlich kann  bei  Reich-
weitenproblemen die  eingebaute Repeaterfunktion  aktiviert  werden.  Geeignet als 
Reiheneinbaugerät für die Verteilermontage, Breite 4TE. 
 

GE NE R AL  

The  Omnio  actuators  (receivers)  are  controlled  by  radio  signals  coming  from  the 
Omnio transmitters. Each transmitter is able to control an unlimited number of ac-
tuators. The radio transmitter can be manually programmed and deprogrammed to 
an actuator following a simple procedure. Via actuator each transmitter can be given 
a certain function and different parameters.  
 
With ARCO technology, all Omnio actuators can be configured completely by radio 
without manual access to the device. The powerful software E-Tool constitutes the 
key component for convenient  planning, configuring  and documenting projects of 
any size right at your desk. 

P RODUC T  D E S CRI P TI O N   

The Omnio DIN rail mounted multi thermostat actuator 8-channels REGH12/08 is a 
device to regulate control valves in floor heatings or similar electric loads through a 
two-point controller with hysteresis. Each of its eight potential free outputs is able 
to  be  controlled  by  an  Omnio  room  sensor  RTF  and  up  to  eight  Omnio  window 
contacts or -handles in AND-operation. The room sensor transmits temperature and 
setpoint to the thermostat actuator by radio. The desired room temperature can be 
set on the room sensor using the control buttons, but it can also be specified by a 
higher-level  system.  Various  operating  modes  such  as  night  setback  can  be  se-
lected via Omnio radio transmitters. If the temperature falls below 8 °C or if the room 
sensor is defective, the frost protection function is automatically activated. Bidirec-
tional communication, EEP D2-34-02. ARCO ready (AWAG Remote Commission-
ing).  In  addition,  this  actuator  can  be  used  as  repeater  in  case  of  range  issues. 
Suitable for DIN rail mounting, width 4 TE. 
 
 

AN ZE I GE -  UN D  BE DI E NE LE M E NTE  

Klemmen 

  1 

Speisung (+) 12 VDC 

  2 

Speisung (-) GND 

  3-5 

Abschirmung 

  6 

RS485 GND 

  7 

RS485 Signal B 

  8 

RS485 Signal A 

  9-11 

Kanal 1 und 2 

 

  12-14 

Kanal 3 und 4 

  15-17 

Kanal 5 und 6 

  18-20 

Kanal 7 und 8 

  S 

Stellventile 

 
Bedienelemente 

  CLR 

Taste und LED Clear 

  LRN 

Taste und LED Learn 

  HEX 

Drehschalter 0..15 

  SEG 

7-Segment Anzeige 

  RT 

RS485 Abschlusswiderstand 120 Ω 

 

DI S P L AY  AN D  OP E R ATI N G  E LEM E NTS  

Terminals  

  1 

power supply (+) 12 VDC 

  2 

power supply (-) GND 

  3-5 

shield 

  6 

RS485 GND 

  7 

RS485 signal B 

  8 

RS485 signal A 

  9-11 

channel 1 and 2   

  12-14 

channel 3 and 4 

  15-17 

channel 5 and 6 

  18-20 

channel 7 and 8 

  S 

control valves 

 
Operating elements 

  CLR 

button and LED clear 

  LRN 

button and LED learn 

  HEX 

rotary switch 0..15 

  SEG 

7-segment display 

  RT 

RS485 terminal resistor 120 Ω 

 

 

 

 

EnOcean-Technologie (868 MHz) 

Summary of Contents for REGH12/08M

Page 1: ...tentialfreien Aus g nge k nnen von je einem Omnio Raumf hler RTF und bis zu 8 Omnio Fenster kontakten oder griffen in UND Verkn pfung angesteuert werden Der Raumf hler sendet Temperatur und Sollwert p...

Page 2: ...Tabelle 4 GER TEPARAMETER zu finden 1 Drehschalter HEX gem ss Tabelle 4 Spalte 1 einstellen 2 Einlernmodus durch einen langen Tastendruck 2 s auf LRN aktivieren LRN leuchtet und CLR blinkt die 7 Segm...

Page 3: ...sem Fall auch ein Temperaturf hler ohne Sollwert wel cher anstelle der Grundfunktion H01 als Funktion H09 Temperatur von Raumf hler eingelernt wird EXTERNER SOLLWERT Der Sollwert kann auch durch ein b...

Page 4: ...andle 2x H05 Window handle Same behaviour as function H04 tilted counts as open Gekippt z hlt als geschlossen 5 Tilted counts as closed H06 Zweiter Sollwert Raumf hler mit EEP A5 10 10 12 Nur der Soll...

Page 5: ...ANSMITTERS Alle Sender l schen 0 2 s dr cken press 2 s 15 LRN Taste 2 s dr cken press LRN button 2 s Delete all transmitters WERKSEINSTELLUNGEN FACTORY SETTINGS Auf Werkseinstellungen zur cksetzen Ach...

Page 6: ...1 Stunde 1 1 hour 2 Stunden 2 2 hours 3 Stunden 3 3 hours 4 Stunden 4 4 hours 5 Stunden 5 5 hours 6 Stunden 6 6 hours 7 Stunden 7 7 hours 8 Stunden 8 8 hours 9 Stunden 9 9 hours 10 Stunden 10 10 hours...

Page 7: ...halb eines Umkreises von 5 Metern darf nur ein Ger t als Repeater aktiviert werden REPEATER In case of problems with the reception quality the repeater function can be activated The actuator will ampl...

Page 8: ...module EnOcean Equimpent Profile EEP D2 34 02 EnOcean Equipment Profile EEP Umweltbedingungen 20 40 C 5 90 rH non condensing Environment Geh use Noryl UL 94 90 x 70 x 59 mm Housing Gewicht 160 g Weigh...

Reviews: