Safety Accessories Supplementary Sheet
36
OMICRON
CPC 100 User Manual
Contains safety and operation instructions for the
CPC 100
test system.
CPC 100 Reference Manual
Contains detailed hardware and software information for the
CPC 100
test system including relevant safety instructions.
CPC 100 PTM User Manual
Contains information on how to use
Primary Test Manager
(PTM)
with
CPC 100
test system.
TESTRANO 600 Getting Started
Contains safety information and use case examples for the
TESTRANO 600
test system.
TESTRANO 600 User Manual
Contains safety and operation instructions for the
TESTRANO 600
test system.
6.2
Operation
The
SAA3
3-Position Remote Safety Switch
has three operating positions shown in the following figure.
Figure 15: Operating positions of the
SAA3
3-Position Remote Safety Switch
Table 21:
SAA3
operating positions
Operating position
Action
Description
I
Do not press the switch.
Emergency-stop is activated.
II
Press the switch into the middle position.
No activation of emergency-stop.
III
Press the switch all the way.
Emergency-stop is activated.
6.3
Connection
To connect the
SAA3
3-Position Remote Safety Switch to the main device:
1. Make sure that the test system´s main device used with the
SAA3
is switched off.
2. Press the
Emergency Stop
button on the main device or test system and lock the main device with
a physical key (
CPC 80
and
CPC 100
)
or by pressing the software lock button (
TESTRANO 600
).
NOTE!
CIBANO 500
and
COMPANO 100
do not have a separate physical key nor a software lock
function.
3. Remove the
Safety Connector Dongle
from one of the
SAFETY
output connectors on the main
device side panel and store it for later use.