CPC 100 V1.41
6 - 18
TRTapCheck (for OLTC)
Use the
TRTapCheck
test card to measure the winding resistance of the
individual taps of a power transformer’s tap changer, and to check whether the
on-load tap changer (OLTC) switches without interruption.
CPC 100
injects a constant current from the
6A DC
output into the power
transformer and the current is led via the
IAC/DC
input for measurement.
Alternatively, the current injected from the
400A DC
output is measured
internally. From this current value and the voltage measured by the
V DC
input
(see Figure 12), the winding resistance is calculated.
In the moment the tap is changed, the
IAC/DC
measuring input detects the
sudden, very short drop of the current flow. A properly working tab change
differs from a malfunctioning one, for example, an interruption during the
change, by the magnitude of the ripple and slope values. An interruption will
result in much higher ripple and slope values than a properly functioning tab
change.
The ripple and slope values are indicated at the
TRTapCheck
test card’s
measurement table (refer to Figure 13).
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...