Measurement setup
4.1.2
Disconnecting the CPC
1. After testing, switch off the
CPC
outputs immediately by pressing the
Start/Stop
button.
2. When the green light is on and the red light is off, turn the key to "lock" (vertical) and remove the key.
If in doubt, press the
Emergency Stop
button.
3. After turning off the
CPC
outputs, earth-connect and short-circuit the test object’s terminals again
using a grounding set.
4. Remove the connection between the
CPC
and the test object.
5. Remove the barrier.
4.2
Cleaning
► Use a cloth dampened with isopropanol alcohol to clean
CPC
and its accessories.
WARNING
Death or severe injury caused by high voltage or current possible
► Do not enter the high-voltage test area as long as the red light on the
CPC
front panel
is flashing. If in doubt, press the
Emergency Stop
button.
► Do not touch any terminals and housing components without a visible ground
connection.
WARNING
Death or severe injury caused by high voltage or current possible
► Do not clean
CPC
when connected to the test object.
► Disconnect the test object, accessories and connection cables before cleaning.