CPC 100
V 3.20
Introduction - 3
Test Cards
The
CPC 100
software comprises a number of test cards. A test card carries out one specific
test, e.g., measuring a CT excitation curve, or testing the ratio of a voltage transformer.
A test card holds a number of user-definable test settings and - after the test was run - test
results.
Test Procedure
A test procedure contains multiple test cards.
The composition of such a test procedure and the settings of all single test cards can be freely
defined by the user. Within a test procedure, each test card and its associated test is executed
individually in a user-defined order.
Report
For archiving or reporting purposes, or later processing, a test procedure with all of its test cards,
specific settings and - after the test was run - test results and assessments can be saved. It is
then considered a report.
Such a report can later be opened any time in the
CPC 100
’s
File Operations
menu.
Note:
For detailed information about test cards, test procedures and templates, refer to section
“How to Use The CPC 100 Software” of chapter “Introduction” in the CPC 100 Reference
Manual available in PDF format on the
CPC 100 Toolsets
or
CPC 100
Start Page
.
+
Rectifier
& power
factor
corrector
Filter
Switched
mode
amplifier
500V 4A
1kV 2A
2kV 1A
500V
500V
500V
500V
65V
65V
3.15A
6.3A
ADC
I
U
U
U
U
I
I
DSP
(Digital
Signal
Processor)
Built-in
ePC
Ethernet
RS 232
optional
optional interfaces
(plug-in boards)
analog or digital
2kV
800A
R
R
-
+
5V / 400A DC
10A AC/DC
3V AC
300V AC
10V DC
BIN IN
65V / 6A DC
6V / 800A AC
2kV
Ext.
Booster
130V / 6A AC
Mains
100-240V
50/60Hz
to
ext.
PC
I
n
p.
O
u
t
p
u
t
s
L
N
PE
Focus on the data entry field for AC current.
The term “focus” designates the currently selected (active) part of the test card. The selected
component is highlighted or inverted.
The actual function of the context-dependent
menu keys depends on the selected view, test
mode, test card and selected test card
component (i.e., the focus).
Temperature and power consumption
monitoring.
If an output is activated, both the
CPC 100
’s
power consumption and the current emitted at
the high-current outputs is monitored and,
together with the temperature, displayed by this
temperature gauge.
The temperature gauge’s bar therewith
represents an indicator for the remaining time
the
CPC 100
can output power.
plenty of spare
no more spare
Status of test assessment. The test
assessment is a manual procedure carried
out by the user. After the test, set the focus
on the assessment symbol. Use the context-
dependent menu key
OK
or
Failed
to assess
the test.
For a few seconds, the status line also
displays general operation information, e.g.
“Emergency key pressed”.
Pressing the
Settings
menu key opens the
Settings
page (see page Quick-1) allowing you to
set the test cards individually. As a rule, do not set the test cards on the
Settings
page but set
all test cards of a test procedure using the
Device Setup
tab in the
Options
view (see page
Introduction-5).
CPC 100
Block Diagram
Principles of Test Cards and Test Procedures
The Components of a Test Card