CP TD1
CP TD1 - 2
CP TD1
The equipment trolley holds the
CPC 100
,
CP TD1
and all required cables. The trolley is
equipped with a grounding bar with three knurled screws to ensure a solid grounding to
equipotential ground of all devices.
If the
CPC 100
and
CP TD1
are to be operated without trolley, place them on their transport
cases and connect them with the long type data cable
CPC 100
CP TD1
(3 m) and the long-
type booster cable
CPC 100
CP TD1
(3 m). Each device has to be grounded separately with
a 6 m grounding cable of at least 6 mm².
Cable drum with
double-shielded
output cable to feed
the high voltage to the
test object
Equipment trolley
CPC 100, CP TD1
and
the equipment trolley
connected to the
trolley’s grounding bar
and led to earth.
Grounding cable min.
6 mm².
Equipotential ground
Booster cable
CPC 100
CP TD1
(short type). Via this
cable the
CPC 100
controls the
CP TD1
output voltage.
CPC 100
CP TD1
Swiveling mounting brackets for the
CPC 100
(top)
and
CP TD1
(bottom)
The
CP TD1
’s measuring inputs IN A
and IN B, connected to the cable drum
for the measuring cables
Data cable
CPC 100
CP TD1
(short
type). Via this data cable the
CPC 100
software (test card
TanDelta
) controls
the
CP TD1
.
To secure the
CPC 100
while pulling the
trolley, a safety belt is available (not
shown).
Functional Components
Setup of Devices with and without Trolley
Cable drum for
measuring
cables
High-voltage
output with
attached screw
plug and yellow
grounding plug.