CP CR500
14
4.2 Connecting CPC 100 to CP TD1
First, connect
CPC 100
with
CP TD1
as follows:
1. Switch off
CPC 100
at the main power switch.
2. Properly connect the
CPC 100
's and
CP TD1
's grounding terminals to earth.
Use cables of at least 6 mm² cross-section.
3. Connect
CP TD1
's "BOOSTER IN" to
CPC 100
's "EXT. BOOSTER". Use
only the booster cable supplied by OMICRON.
4. Connect
CP TD1
's "SERIAL" to
CPC 100
's "SERIAL". Use only the data
cable supplied by OMICRON.
The data cable also provides the power supply for
CP TD1
.
4.3 Connecting the CP CR500 to a CPC 100
(Safety Circuit)
1. Remove the dongle from
CPC 100’s "
connector for external safety functions"
(at the right side of
CPC 100).
2. Connect the Safety A connector at the
CP CR500
interface panel to
CPC 100’s
connector for external safety functions using the modem cable
(length 9 meter).
3. Terminate the Safety B connector at the
CP CR500
interface panel with the
CPC 100
dongle that is normally plugged in at the
CPC 100’s
connector for
external safety functions.
If you use two
CP CR500
, please refer to 4.6 ”Connecting Two CP CR500
Summary of Contents for CP CR500