Operating and Configuring the CT Analyzer
The following values can be defined in the
Miscellaneous Settings
page.
Assessments
Check "*" settings
before start
Display warning
before start
Depending on the selected standard and CT type,
some parameters and data (for example, the nominal
burden) are required to obtain a correct assessment of
the CT. If the user does not specify these data prior to
the test, the automatic assessment function of the
CT Analyzer
possibly performs the assessment based
on the actual values determined for the CT during the
test and not based on the CT’s nominal data stated on
the name plate.
"Check "*" settings before start"
If this option is enabled, the
CT Analyzer
checks
whether the user has entered all necessary values and
data relevant for an automatic assessment prior to the
test start. The respective parameters are then marked
by a star ("*") in the
CT-Object
card. If the user did not
enter data for one or more of these mandatory
parameters, no automatic assessment is performed
and the
CT Analyzer
displays an "Assessment not
available" message after the test is finished.
This option can be used to avoid an automatic
assessment if the user did not enter all required
parameters and CT data prior to the test.
"Display warning before start"
This option is only relevant if the "Check "*" settings
before start" option is enabled. It is enabled
automatically when enabling the "Check "*" settings
before start" option but can be disabled manually.
Enabling the "Display warning before start" option
displays a corresponding warning message prior to the
test start if the user did not enter data for one or more
of the mandatory parameters that are required for
assessment.
Continuous burden
measurement
Normally, the
CT Analyzer
stops the burden test
automatically as soon as it obtains stable
measurement values for the connected burden.
If this option is enabled, the burden measurement is
not stopped automatically but instead performed
continuously until the user stops it manually by
pressing the
key.
I/0
I/0
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...