67
Operating and Configuring the CT Analyzer
Temperature
Select the temperature unit (
°C
or
°F
) and the default
values for the ambient temperature and the reference
temperature (for winding resistance measurement and
calculation).
Date/Time
Clock settings for the device-internal clock.
Display Contrast
Display contrast adjustment.
Accur. Limiting
Error Graph
Enable or disable the accuracy limiting error graph.
This graph is primarily required for Chinese standards. It
shows the maximum possible primary current (K * I
pn
)
that can flow over a specific burden without exceeding the
accuracy limit (5% or 10%).
Start Delay
Allows the definition of a delay time of up to 10s for the
actual test start after pressing the start button.
You can apply the defined delay for the burden test, the
residual magnetism measurememt, the primary winding
resistance measurement and the secondary winding
resistance measurement.
Min. VA at M cores
Isn 5A
Applies to IEC 60044-1 metering CTs with I
sn
= 5A only!
Here you can set the minimum VA value used for the CT
assessment to
3.75VA
. This means, selecting the
3.75VA
soft key will cause the
CT Analyzer
to assess the
CT only up to a lower nominal burden limit of 3.75VA
instead of 1VA. When 3.75VA is active, it is not possible
to enter VA values lower than 3.75VA in the
CT-Object
card.
Selecting
0VA
deactivates this option. Assessment is
then performed up to a lower burden value of 1VA. This
is the factory default which is suitable for most cases.
You should not change it without important reason.
C57.13 electronic
burdens
Applies to IEEE C57.13 metering CTs only!
Enable or disable the use of the electronic burdens E-0.2
and/or E-0.04 for CT Assessment. If enabled, these
values are offered in the set of soft keys available for the
"VA" and "Burden" parameters in the
CT-Object
card. In
this case, CT assessment is also performed for the
electronic burden values in addition to the burden values
defined in the standard.
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...