149
Using the Quick Test Feature
8.6
CT Ratio Measurement
This is a predefined measurement type, intended especially for the quick
measurement of CT ratios.
To select the CT Ratio measurement type, use the
cursor key to move the
cursor to the
Measurement Type
field in the
CT-Quick
card and then press the
CT Ratio
soft key.
Figure 8-9
CT-Quick
card and
Results
card for CT ratio measurement
For the
CT Ratio
measurement type, the
CT-Quick
card holds the following
measurement quantities:
Caution:
CT ratio measurement using
Quick Test
is not a complete CT test!
This measurement only determines the current ratio of CTs. The
CT Analyzer
does not perform automatic demagnetization after the measurement.
Parameter
Description
Output
The output signal type is fixed to "AC".
U/I
Operating mode of the internal signal generator: voltage or
current source. Fixed to "Voltage".
Amplitude
RMS voltage of the output signal. Adjustable by the user.
Possible values: 0 to 40V. Default: 1.00V.
f
Frequency of the output signal. Adjustable by the user.
Possible values: 5.0 to 400.0Hz or soft keys
16.7Hz
,
50Hz
,
60Hz
or
400Hz
.
Default: 50Hz
Load
Fixed to "On".
Setting the
Load
parameter to "on" and specifying the winding
resistance and the unsaturated inductance in the fields
R
and
L
will prevent saturation of the connected CT.
The output generator of the
CT Analyzer
then keeps the DC part
of the output current at zero using a current regulator
permanently running during the output of AC signals.
Press the
Main
soft key in
any test card
Main Menu:
- New Quick-Test
OK
soft key
CT-Quick
card:
Measurement Type:
CT Ratio
How to get there:
Summary of Contents for CT Analyzer
Page 1: ...CT Analyzer CT SB2 User Manual...
Page 3: ...CT Analyzer User Manual...
Page 4: ...CT Analyzer User Manual 2 Manual Version CTAnalyzerUM AE 3...
Page 39: ...37 Setup and Connection Figure 2 15 Measurement setup for delta compensation Ratio 1 L2 L3 L1...
Page 50: ...CT Analyzer User Manual 48...
Page 60: ...CT Analyzer User Manual 58...
Page 80: ...CT Analyzer User Manual 78...
Page 162: ...CT Analyzer User Manual 160...
Page 172: ...CT Analyzer User Manual 170...
Page 188: ...CT Analyzer User Manual 186...
Page 194: ...CT Analyzer User Manual 192...
Page 195: ...CT SB2 User Manual...
Page 196: ...CT SB2 User Manual 2 Manual Version CTSB2 AE 3...
Page 204: ...CT SB2 User Manual 10...
Page 206: ...CT SB2 User Manual 12...
Page 211: ...17 Hardware 1 x Cable bag Bag for cables and accessories Accessories Description...
Page 212: ...CT SB2 User Manual 18...
Page 226: ...CT SB2 User Manual 32...
Page 242: ...CT SB2 User Manual 48...
Page 248: ...CT SB2 User Manual 54...
Page 250: ...CT SB2 User Manual 56...
Page 252: ...CT SB2 User Manual 58...