Pressure Transducer

PX276 and PX279

Pressure Transducer

PX276 and PX279

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

M3505/0816

Pressure Transducer

PX276 and PX279

Pressure Transducer

PX276 and PX279

Pressure Transducer

PX276 and PX279

Pressure Transducer

PX276 and PX279

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 

SPECIFICATIONS

Inspection

Requirements

Mounting

INSTALLATION

Inspect the package for damage. If damaged, notify the appropriate carrier 

immediately.  If undamaged, open the package and inspect the device for 

obvious damage. Return damaged products.

Warning:

•  Do not use on oxygen service, in an explosive/hazardous environment, or 

with flammable/combustible media.

•  Disconnect power supply before installation to prevent electrical shock 

and equipment damage.

•  Make all connections in accordance with the job wiring diagram and in 

accordance with national and local electrical codes. Use copper 

conductors only.

Caution:

•  Use electrostatic discharge precautions (e.g., use of wrist straps) during 

installation and wiring to prevent equipment damage.

•  Avoid locations where severe shock or vibration, excessive moisture or 

corrosive fumes are present. NEMA Type 4 housings are intended for 

outdoor use primarily to provide a degree of protection against wind-blown 

dust, rain, and hose-directed water.

•  Do not exceed ratings of the device.

Refer to 

Figure 7

 for mounting dimensions.

1.  Remove the transducer cover using a Phillips head screwdriver.
2.  Select the mounting location.
3.  Mount transducer on a vertical surface with two #8 self-tapping screws 

(not provided).

4.  Pull wires through bottom of enclosure and make necessary connections.
5.  Replace cover and make pneumatic connections.

• Tools (

not provided

)

-  Digital Volt-ohm Meter (DVM)

-  Appropriate screwdriver for mounting screws

-  Appropriate drill and drill bit for mounting screws

•  Appropriate accessories
•  Two #8 self-tapping mounting screws (not provided)
• Training: 

Installer must be a qualified, experienced technician

PX276 Duct Pressure Transducer with mA Output

Wiring PX276 Units with mA Output

Wiring PX279 Units with VDC Output

PX279 Duct Pressure Transducer with VDC Output

TYPICAL APPLICATIONS (wiring diagrams)

Input Signal

+

Common

+

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

12–40 VDC Power Supply

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

mA Output Transducer Only

Figure 1 

and 

Figure 2 

illustrate typical wiring diagrams for the PX276 Series, 4–20 mA,

two-wire output duct pressure transducers.

Figure 1

 – 

Wiring for mA Output Duct Pressure Transducers with External DC 

Power Supply

Figure 2 

– 

Wiring for mA Output Duct Pressure Transducers where the Controller or 

Meter has an Internal DC Power Supply

Figure 3 

and

 Figure 4 

illustrate typical wiring diagrams for the PX279, 0–5/0–10 VDC 

output duct pressure transducer.

Figure 3 

– 

Wiring for VDC Output Duct Pressure Transducers when applied with

External AC Supply.

Signal

+

Common

Supply

Neutral

Hot

O

Input Signal

+

Common

+

Shield/Ground

Controller / Meter / Recorder

VDC Output Transducer Only

12–35 VAC Transformer

Accuracy*:

  ± 1% FS

Overpressure:

  10 PSID

Supply Voltage:

  12–40 VDC

                              12–35 VAC (VDC output units only)

Supply Current:

  VDC Units – 10 mA max.

                               mA Units – 20 mA max.

Enclosure:

  18 Ga C. R. Steel NEMA 4 (IP-65)

                      6061T aluminum probe

Finish:

  Baked on enamel – PMS2GR88B

Conformance:

  EMC Standards EN50082-1(1992)

                            EN55014(1993)/EN60730-1(1992)

Compensated Temp Range:

  25°F to 150°F (-4°C to 65°C)

T. C. Error:

  ±0.0125%/°F (.02%/°C)

Operating Temp Range:

  0°F to 175°F (-18°C to 80°C)

Media Compatibility:

  Clean dry air or any inert gas

Environmental:

  10–90%RH Non-Condensing

Termination:

  Unpluggable screw terminal block

Wire Size:

  12 Ga max.

Load Impedance:

  3K ohms max. at 40 VDC (mA output units)

                                 1K ohms min. (VDC output units)

Weight:

  Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

Wiring

Use maximum 12 AWG wire for wiring terminals.  Refer to 

Figures 1, 2, 3, 

&

 4

 

for wiring information and 

Figures

 

5

 & 

6

 for switch designations.

MAMA

C

9248

S1

S2

ON

ON

Zu

Zb

S

Zu

S

S1

S2

Zu

Zb

S

+

0

S3

ON

ON

ON

MAMA

C

9248

Zu

S

PX276 pressure transducers with 4–20 mA output units are powered with a 12–40 VDC supply.
The following describes the proper wiring of these pressure transducers with mA output:
1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+] and [-] terminal markings on the board.
3.  Attach the supply voltage to the [+] lead.
4.  Connect the 4–20 mA output ([-] terminal) to the controller’s input terminal.
5.  Ensure that the power supply common is attached to the common bus of the controller. 
6.  Re-insert the terminal block to the circuit board and apply power to the unit.
7.  Check for the appropriate output signal using a DVM set on DC milliamps connected in 

series with the [-] terminal. 

PX279 pressure transducers with VDC output are field selectable 0–5 VDC or 0–10 VDC 

output and can be powered with either 12–40 VDC or 12–35 VAC.

The following describes the proper wiring of these pressure transducers with VDC output:

1.  Remove the terminal block by carefully pulling it off the circuit board.
2.  Locate the [+], [-] and [0] terminal markings on the board.
3.  Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the 

negative output terminal. 

4.  Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s input 

terminal. 

5.  Re-insert the terminal block to the circuit board and apply power to the unit.
6.  Check the appropriate VDC output using a voltmeter set on DC volts across the [0] and [-] 

terminals. 