Test And Adjusting Gas Pressure
NATURAL GAS –
Appliance test point located at the regulator
The supplied regulator must be fitted to the appliance inlet connection. Gas pressure must be adjusted to
1.0 kPa when approximately 50% of the burners are on a high setting.
UNIVERSAL LPG –
Appliance test point located at the burner injector
Gas pressure must be checked to confirm the appliance operating pressure is 2.75 kPa, the appliance test
point is the rapid burner injector as shown below.
1. Disconnect power
2. Manually light the auxiliary burner and set to high flame
3. Zero manometer, then apply flexible tubing to seal over the rapid burner injector, hold securely in
place and check the gas pressure by pressing in the corresponding burner control knob on high
flame position.
4. If the pressure is 2.75 kPa, reassemble the burner and perform the final checks as per this
instruction manual.
5. If the pressure is
not
2.75 kPa, disconnect the appliance and check/adjust/replace the LPG cylinder
regulator(s) in accordance with AS/NZS 5601.
If the appliance is supplied with an LPG test point adaptor, then this component may be fitted to the
inlet connection for the purpose of a test point.