background image

DMD4380 

DMD4380-DC 

DC-DC Isolated Transmitter

M-5001/0219

Lifetime

TM

MADE IN

Model

Power

DMD4380

85-265 VAC, 50/60 Hz or 60-300 VDC

DMD4380-DC

9-30 VDC or 10-32 VAC

Description

The DMD4380 is a field-rangeable signal isolator/transmitter/con-

verter. It accepts a DC voltage or current input and provides an 

optically isolated DC voltage or current output that is linearly related 

to the input. Full 3-way isolation (input, output, power) makes this 

module useful for ground loop elimination, signal conversion and 

isolation, common mode signal rejection, or noise pickup reduction.
Standard on the DMD4380 is a 15 VDC loop excitation supply for the 

input and a 20 VDC loop excitation supply for the output. These power 

supplies can be selectively wired to power passive mA devices. 
A green input LED and a red output LED vary in intensity with changes 

in the process input and output signals. These provide a quick visual 

picture of your process loop at all times. 
An output test button provides a fixed output (independent of the 

input) when held depressed. The test output level is potentiometer 

adjustable from 0 to 100% of output span. 
The I/O LEDS and the output test button greatly aid in saving time 

during initial startup and/or troubleshooting.

DC Input Ranges

Field selectable ranges and offsets via switch settings

Voltage: 

0-10 mVDC  to  0-130 VDC 

Bipolar voltage: 

±5 mVDC 

to  ±65 VDC 

Current: 

0-200 µADC  to  0-50 mADC 

Input offset: 

±100% in 15% increments

Input Impedance (Voltage)

Voltage: 

1 M

 minimum 

Current: 50 

 typical 

Voltage burden: 

 1 VDC at 20 mA current input

Common Mode Rejection

100 dB minimum

Input Loop Power Supply

15 VDC ±10%, regulated, 25 mADC 

May be selectively wired for sinking or sourcing mA input

LoopTracker

Variable brightness LEDs indicate I/O loop level and status

DC Output Ranges

Field selectable ranges and offsets via switch settings

Voltage (10 mA max):  0-1 VDC 

to  0-10 VDC  

Bipolar voltage: 

±5 VDC 

or  ±10 VDC 

Current: 

0-2 mADC  to  0-20 mADC, 4-20 mADC 

 

20 V compliance, 1000 

 at 20 mA

Output Calibration

Multi-turn zero and span potentiometers 

±15% of span adjustment range typical

Output Loop Power Supply

20 VDC nominal, regulated, 25 mADC, <10 mVRMS max. ripple

May be selectively wired for sinking or sourcing mA output

Output Test/Override

Front button sets output to test level when pressed or via external 

contact closure 

Potentiometer adjustable 0-100% of span

Output Ripple and Noise

Less than 10 mVRMS ripple and noise

Linearity

Better than ±0.1% of span

Ambient Temperature Range and Stability

–10°C to +60°C operating ambient 

Better than ±0.02% of span per °C stability

Response Time

70 milliseconds typical 

DF option: 1 millisecond typ. (output noise will exceed specifications)

Isolation

1200 VRMS minimum 

Full isolation: power to input, power to output, input to output

Housing and Connectors

IP 40, requires installation in panel or enclosure

For use in Pollution Degree 2 Environment 

Mount vertically to a 35 mm DIN rail 

Four 4-terminal removable connectors, 14 AWG max wire size

Power

85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum 

D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum

e-mail: [email protected] 

For latest product manuals: 

www.omegamanual.info

Shop online at 

omega.com

User’s Guide

1 2 3 4

5  6 7 8

9 10 11 12

13 14 15 16

Input

Remote Test

Output

Power

Do not connect 

anything to 

unused terminals

WARNING:

 This product can expose you to chemicals includ-

ing nickel, which are known to the State of California to cause 

cancer or birth defects or other reproductive harm. For more 

information go to www.P65Warnings.ca.gov

13  Power AC or DC +
14 

Earth Ground

16  Power AC or DC –

14

13

15

16

2

1

3

4

Voltage Output 

Switch E set to “V”

– 

+

Voltage 

Device

2

1

3

4

Current Sourcing Output  

Switch E set to “I” 

– 

+20V

mA 

Device

R

i

mA 

Xmtr

R

i

10

9

11

12

+15V 

 –

Current Sourcing Input

10

9

11

12

– 

+

Voltage Input

Voltage 

Xmtr

To maintain full isolation avoid 

combining power supplies in 

common with input, output, or 

unit power.

6

5

7

8

External Contact  

for Test Function

Cu 60/75°C 

conductors 

14 AWG 

max.

Current Sinking Output

 

switch E set to “I”

2

1

3

4

– 

+

+

 –

Loop 

Power 

Source

+

4-20 mA 

Device

R

i

Current Sinking Input

– 

+

+

Loop 

Power 

Source

mA 

Xmtr

R

i

10

9

11

12

Variable Brightness Output Indicator
Output Test Level Adjustment

Push to Test Output

Output Span Calibration

Variable Brightness Input Indicator

Output Zero Calibration

 

Omega Engineering Inc.

Test Cal.

Span

Zero

Test

DMD4380

DC to DC

Isolated Transmitter

Output 
LED

Input 
LED

Pb

Lead 

Free

Wire terminal torque 

0.5 to 0.6 Nm or 

4.4 to 5.3 in-lbs

Summary of Contents for DMD4380

Page 1: ...25 mADC 10 mVRMS max ripple May be selectively wired for sinking or sourcing mA output Output Test Override Front button sets output to test level when pressed or via external contact closure Potentiometer adjustable 0 100 of span Output Ripple and Noise Less than 10 mVRMS ripple and noise Linearity Better than 0 1 of span Ambient Temperature Range and Stability 10 C to 60 C operating ambient Bett...

Page 2: ...nd the corresponding output change from minimum to maximum For current outputs the red LED will only light if the output loop cur rent path is complete For either current or voltage outputs failure to illuminate or a failure to change in intensity as the process changes may indicate a problem with the module power or signal output wiring Note that it may be difficult to see the LEDs under bright l...

Page 3: ...7I B503I 0 13 V 3400V 3408V 3401V 3406V 3409V 3402V 3407V 3403V 3404V 3405V 3400I 3408I 3401I 3406I 3409I 3402I 3407I 3403I 0 16 V 9400V 9408V 9401V 9406V 9409V 9402V 9407V 9403V 9404V 9405V 9400I 9408I 9401I 9406I 9409I 9402I 9407I 9403I 0 20 V 1C00V 1C08V 1C01V 1C06V 1C09V 1C02V 1C07V 1C03V 1C04V 1C05V 1C00I 1C08I 1C01I 1C06I 1C09I 1C02I 1C07I 1C03I 0 25 V 2800V 2808V 2801V 2806V 2809V 2802V 280...

Page 4: ...by OMEGA if the unit is found to be defective it will be repaired or replaced at no charge OMEGA s WARRANTY does not apply to defects resulting from any action of the purchaser including but not limited to mishandling improper interfacing operation outside of design limits improper repair or unauthorized modification This WARRANTY is VOID if the unit shows evidence of having been tampered with or ...