Step 30. Select the Deviation Control Type Submenu

Press 

d

. If flashing 

_DEV

Deviation is displayed press 

a

,

otherwise press 

b

until flashing 

_DEV

is shown. Now 

press 

d

to store and go to next menu item. 

Step 31. Select the Latched Type Submenu

Press 

d

. If flashing 

UNLT

Unlatched is displayed press 

a

,

otherwise press 

b

until 

UNLT

is displayed. 

Press 

d

to store and advance to next menu item.

Step 32. Select the Normally Open Type of Contact
Closure Submenu

Press 

d

. If flashing 

N.o.

Normally Open is displayed, 

press 

a

, otherwise press 

b

until 

N.o.

is displayed. Press 

d

to store and advance to next menu item.

Step 33. Select the Above Type of Active Submenu

Press 

d

. If flashing 

ABoV

Above is displayed, press 

a

,

otherwise press 

b

until 

ABoV

is displayed. Press 

d

to store

and advance to next menu item.

Step 34. Enable Alarm 1 at Power On (

A.P.oN

)

Press 

d

. If flashing 

ENBL

is displayed, press 

a

, otherwise

press 

b

until 

ENBL

is displayed. Press 

d

to store and

advance to next menu item.

Step 35. Enter Alarm 1 High Submenu

Press 

a

twice to skip 

ALR.L

Alarm 1 Low value. 

ALR.L

is

for below & 

ALR.H

for above.

Step 36. Set the Alarm 1 High value (

ALR.H

)

Press 

d

. Press 

b

or 

c

until value to set the display to

002.0

. Press 

d

to save.

Step 37. Enter the Alarm 2 Menu

The display will show 

ALR2

the top menu for Alarm 2.

Repeat steps from 28 to 36 to set for Alarm 2 the same
conditions as for Alarm 1.

Step 38. Skip the Loop Break Time Menu (

LOOP

)

Press 

a

to go to the 

OUT1

Output 1 Menu item.

Step 39. Configuration the Output 1 Menu 

Set Alarm 1 Disabled (Step 29) to be able to Enable
Output 1. 

Configure Out 1 as 

CTRL

PID

,

ACTN

RVRS

,

AUTO

/

DSBL

ANTL

ENBL

,

PRoP

005.0

,

REST

0180

,

RATE

/

018.0

CYCL

0010

and 

DPNG

0003

. Please refer to the

operator’s manual if needed. Press 

d

to save and go to the

next menu item.

Step 40. Configuration of Display Color Selection

Press 

a

until the 

COLR

Display Color Selection Menu

appears on the Display. Configure 

COLR

as 

N.CLR

GRN

(green), 

1.CLR

RED

(red), 

2.CLR

AMBR

(amber). Please

refer to the operator’s manual if needed. 

Step 41. Run a Test

Press 

a

until reset the controller and return to 

RUN

Mode to

display 

075.0

(Ambient Temperature). Now you are ready to

observe temperature as it rises 10°F higher than displayed.
Touch the tip of the Thermocouple to raise the temperature
above the Alarm 2 High value 

082.0

, and AL2 will turn on,

and Display Color will change from Green to Amber.
Continue touching the tip to raise the temperature above the
Alarm 1 High value 

087.0

and Display Color will change

from Amber to Red. Annunciator “1” is turning on and off
displaying output 1.

Step 11. Enter to the Thermocouple Type Input Submenu

Press 

d

to display flashing, previously selected

Thermocouple type.

Step 12. Scroll through available selection of TC types

Press 

b

to sequence thru flashing Thermocouple types,

(select k -for type "K" CHROMEGA

®

/ALOMEGA

®

)

J   K  T E  N   DIN J    R  S  B  C - TC types

J   k   t   E  N    dN J

R  S  b C - Display

Step 13. Store TC type

After you have selected the Thermocouple type press 

d

to

store your selection, the instrument automatically advances
to the next menu item.

Step 14. Enter to Reading Configuration Menu

The display shows 

RDG

Reading Configuration, which is the

top menu for 4 submenus: Decimal Point, Degree Units,
Filter Constant and Input/Reading Submenus.

Step 15. Enter to Decimal Point Submenu

Press 

d

to show 

DEC

Decimal Point.

Step 16. Display the Decimal Point position

Press 

d

again to display the flashing Decimal Point position.

Step 17. Select the Decimal Point position

Press 

b

to select 

FFF.F

Decimal Point position.

Step 18. Store selected Decimal Point position

By pressing 

d

momentarily the Decimal Point position will

be stored and the instrument will go to the next menu item.

Step 19. Enter to Temperature Unit Submenu

Display shows 

TEMP

Temperature Unit.

Step 20. Display available Temperature Units

Press 

d

to display the flashing Degree 

°F

or 

°C

.

Step 21. Scroll through Temperature Units selection

Press 

b

to select 

°F

Degree.

Step 22. Store the Temperature Unit

Press 

d

to display momentarily that the Degree Unit has

been stored and the instrument will go automatically to the
next menu item.

Step 23. Enter the Filter Constant Submenu

Display shows 

FLTR

Filter Constant Submenu.

Step 24. Display the Filter Constant Value Submenu

Press 

d

to display the flashing, previously selected Filter

Constant.

Step 25. Scroll through available Filter Constants

Press 

b

to sequence thru Filter Constants 

0001

0002

,

0004

0008

0016

0032

0064

and 

0128

.

Step 26. Store the Filter Constant

Press 

d

momentarily to store 

0004

Filter Constant and the

instrument will automatically go to the next menu item.

Step 27. Enter Alarm 1 Menu

The display will show 

ALR1

the top menu for Alarm 1. In

the following steps we are going to enable Alarm 1,
Deviation, Unlatch, Normally Open, Active Above, Enable at
power on and +2°F High Alarm i.e. Process Value >
Setpoint 1 Value +2°F will activate Alarm 1.

If Analog Output Option is installed and enabled,
the controller will skip Alarm 1 Menu item to 
Analog Output.

Step 28. Enter Alarm 1 Enable/Disable Submenu

Press 

d

to display flashing 

DSBL

ENBL

.

Step 29. Enable Alarm 1 Submenu

If flashing 

ENBL

is displayed, press 

a

, if 

DSBL

is displayed,

press 

b

until 

ENBL

is displayed, then press 

d

to store and

go to the next menu item.

SPECIFICATION

Accuracy:

+0.5°C temp; 
0.03% rdg. process typical

Resolution:

1°/0.1°; 10 µV process

Temperature Stability:

0.04°C/°C RTD; 
0.05°C/°C TC @ 25°C (77°F); 
50 ppm/°C process

Display:

4-digits, 9-segments LED, 
10.2 mm (0.40") with red, green and
amber programmable colors

Input Types:

Thermocouple, RTD, Analog Voltage
and Current

TC: (ITS90)

J, K, T, E, R, S, B, C, N, L

RTD: (ITS68)

100/500/1000 ohm Pt sensor
2-, 3-, or 4-wire; 0.00385 or 0.00392
curve

Voltage:

0 to 100 mV, 0 to 1 V, 0 to 10 Vdc 

Current:

0 to 20 mA (4 to 20 mA)

Output 1:

Relay 250 Vac @ 3 A Resistive Load,
SSR, Pulse, Analog Voltage and Current

Output 2:

Relay 250 Vac @ 3 A Resistive Load,
SSR, Pulse  

Options: Communication

RS-232 / RS-485 

or

10BaseT

or

Excitation: 24 Vdc @ 25 mA

Exc. not available for Low Power Option

Line Voltage/Power:

90 - 240 Vac ±10%, 50 - 400 Hz*, 

or

110 - 375Vdc, 

4W 

for i16; 

5W 

for i16D

* No CE compliance above 60 Hz

Low Voltage Power Option:

12-36 Vdc, 

3 W

, power for i16 

20-36 Vdc, 

4 W

, power for i16D

**

** Units can be powered safely with 24 Vac

but No Certification for CE/UL are claimed.

Dimensions:

48 H x 48 W x 127 D mm 
(1.89 x 1.89 x 5")

Weight:

159 g (0.35 lb)

Approvals:

UL, C-UL, CE per EN61010-1:2001

CNi16, CNi16D

Temperature & Process

Controller

USA

MADE IN

Servicing North America:

USA:

 

 

         One Omega Drive, P.O. Box 4047

ISO 9001 Certified

 

         Stamford CT 06907-0047

 

 

         TEL: (203) 359-1660 

 

FAX: (203) 359-7700

 

 

         e-mail: [email protected]

Canada:

   

         976 Bergar

 

 

         Laval (Quebec) H7L 5A1

 

 

         TEL: (514) 856-6928 

 

FAX: (514) 856-6886

 

 

         e-mail: [email protected]

For immediate technical or application assistance:

USA and Canada:

           Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA

®

 

 

         Customer Service: 1-800-622-2378 / 1-800-622-BEST

®

 

 

         Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN

®

Mexico and

  

         TEL: (001)800-TC-OMEGA

®

 

FAX: (001) 203-359-7807 

Latin American: 

         

En Español: (001) 203-359-7803 

 

 

         e-mail: [email protected]

Servicing Europe:

Benelux:

  

         Postbus 8034, 1180 LA Amstelveen, The Netherlands

 

 

         TEL: +31 20 3472121 

 

FAX: +31 20 6434643

 

 

         Toll Free in Benelux: 0800 0993344 

 

 

         e-mail: [email protected]

Czech Republic:

 

         Frystatska 184, 733 01 Karviná

 

 

         TEL: +420 59 6311899   

FAX: +420 59 6311114

 

 

         e-mail: [email protected]

France:

   

         11, rue Jacques Cartier, 78280 Guyancourt

 

 

         TEL: +33 1 61 37 29 00  FAX: +33 1 30 57 54 27

 

 

         Toll Free in France: 0800 466 342

 

 

         e-mail: [email protected]

Germany/Austria:

           Daimlerstrasse 26, D-75392 Deckenpfronn, Germany

 

 

         TEL: +49 7056 9398-0   

FAX: +49 7056 9398-29

 

 

         Toll Free in Germany: 0800 639 7678

 

 

         e-mail: [email protected]

United Kingdom:

           One Omega Drive

ISO 9002 Certified

 

         River Bend Technology Centre

 

 

         Northbank, Irlam  Manchester M44 5BD United Kingdom  

 

 

         TEL: +44 161 777 6611  FAX: +44 161 777 6622

 

 

         Toll Free in England: 0800 488 488

 

 

         e-mail: [email protected]

OMEGAnet

®

 On-Line Service

www.omega.com

Internet e-mail

[email protected]

®

®

MQS3354/1104

WARRANTY/DISCLAIMER

OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of

one (1) year

from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will

extend  the  warranty  period  for 

four (4)  additional  years

if  the  warranty  card  enclosed  with  each  instrument  is

returned to OMEGA.

If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will
issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA,
if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply
to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing,
operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit
shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive
corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions  outside  of  OMEGA’s  control.  Components  which  wear  are  not  warranted,  including  but  not  limited  to
contact points, fuses, and triacs.

OMEGA is  pleased  to  offer  suggestions  on  the  use  of  its  various  products.  However,  OMEGA neither
assumes responsibility for any omissions or errors nor assumes liability for any damages that result from
the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA
warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO
OTHER  WARRANTIES  OR  REPRESENTATIONS  OF  ANY KIND  WHATSOEVER,  EXPRESS  OR  IMPLIED,
EXCEPT  THAT  OF  TITLE,  AND  ALL IMPLIED  WARRANTIES  INCLUDING  ANY WARRANTY OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION
OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with
respect  to  this  order,  whether  based  on  contract,  warranty,  negligence,  indemnification,  strict  liability  or
otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event
shall OMEGA be liable for consequential, incidental or special damages.

CONDITIONS:    Equipment  sold  by  OMEGA is  not  intended  to  be  used,  nor  shall  it  be  used:  (1)  as  a  “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications
or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application,
used  on  humans,  or  misused  in  any  way,  OMEGA assumes  no  responsibility  as  set  forth  in  our  basic
WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless
from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.

RETURN REQUESTS/INQUIRIES

Direct  all  warranty  and  repair  requests/inquiries  to  the  OMEGA Customer  Service  Department.  BEFORE
RETURNING ANY PRODUCT(S)  TO  OMEGA,  PURCHASER  MUST OBTAIN AN AUTHORIZED  RETURN  (AR)
NUMBER  FROM  OMEGA’S  CUSTOMER  SERVICE  DEPARTMENT (IN  ORDER  TO AVOID  PROCESSING
DELAYS).  The  assigned AR  number  should  then  be  marked  on  the  outside  of  the  return  package  and  on  any
correspondence.

The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in
transit.  

FOR WARRANTY RETURNS, please have the
following information available BEFORE 
contacting OMEGA:
1.

Purchase Order number under which the product
was PURCHASED,

2.

Model and serial number of the product under
warranty, and

3.

Repair instructions and/or specific problems
relative to the product.

FOR NON-WARRANTY REPAIRS, consult OMEGA for
current repair charges. Have the following information
available BEFORE contacting OMEGA:
1. 

Purchase Order number to cover the COST of the
repair,

2.

Model and serial number of product, and

3.

Repair instructions and/or specific problems
relative to the product.

OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords
our customers the latest in technology and engineering.

OMEGA is a registered trademark of OMEGA ENGINEERING, INC.

© Copyright 2004 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without
the prior written consent of OMEGA ENGINEERING, INC.

PATENT AND TRADEMARK NOTICE: This product is covered by one or more of the following patents:  U.S. Pat.
No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / GERMANY DE
41 34398 C2 / SPAIN 2039150; 2048066 / UK Patent No. GB2 249 837; GB2 248 954 / FRANCE BREVET NO. 91
12756. The “Meter Bezel Design” is a trademark of Newport Electronics, Inc. USED UNDER LICENSE. Other U.S.
and International Patents pending or applied for.

This  device  is  marked  with  the  international  caution  symbol.      It  is  important  to  read  the
Setup Guide before installing or commissioning this device, as the guide contains important
information relating to safety and EMC.

WARNING:

These  products  are  not  designed  for  use  in,  and  should  not  be  used  for,  patient-

connected applications.

It  is  the  policy  of  OMEGA to  comply  with  all  worldwide  safety  and  EMC/EMI  regulations  that  apply.
OEMGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The  information  contained  in  this  document  is  believed  to  be  correct,  but  OMEGA Engineering, Inc.
accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.