with the   (up arrow) button or 

 (Down arrow) 

button. Holding the 

 button and the   (Up)/ 

(Down) button for an extended period will cause 

the setpoint temperature to advance more rapidly to a 

desired value. The minimum and maximum setpoints 

are locked out at 0 and 260°C (32 and 500°F), 

respectively.

Changing the Display Units from °C to °F or  

(°F to °C) 

Press and hold the   (Up) and

(Down) buttons on 

the controller at the same time for 3-4 seconds, then 
release. The display will be flashing between “tune – 
off”. Press the

button one time. The display will be 

flashing between “LEVEL-1”. While holding the 
(Modify) key down press the   button one time. The 
display will be flashing between “LEVEL-2”. Now that 
you are on menu level 2 release the 

 button. Press 

the   button eleven times. The display will now be 
flashing between “unit-°F” or “unit-°C”. To change the 
current units setting press and hold the 

 button, 

then press the   or 

 button one time to change 

between units. To save your change and return to the 
run mode press and hold the   and 

buttons at the 

same time for 3-4 seconds, then release.

Communication (RS-232)

This section only applies to CL1000 Series Calibrators 

purchased with optional RS-232 Communications 

(-C2) Option

Your calibrator unit has been factory pre-wired 

and configured for ease of use with a stereo jack 

connection on the side panel that will require no 

additional wiring. An interface cable, Part No. 

OM-NOMAD-CP9 is included with your unit for easy 

connection between your benchtop calibrator and PC.

ARTWORK/PRODUCT ART/

 DWGS/START HERE ARROW

5

ARTWORK/PRODUCT ART/

 DWGS/START HERE ARROW

6

CL1000 SERIES

Mini hot point

® 

Dry  

Block Probe Calibrator

omega.com   [email protected]

®

Servicing North America:

U.S.A.:

 

 Toll-Free: 1-800-826-6342 (USA & Canada Only) 

Customer Service: 1-800-622-2378 (USA & Canada Only)  

Engineering Service: 1-800-872-9436 (USA & Canada Only) 

Tel: (203) 359-1660 

Fax: (203) 359-7700 

 

e-mail: [email protected]

Canada:

 

 Toll-Free: 1-800-826-6342 (USA & Canada Only)   

Tel: (514) 856-6928 

Fax: (514) 856-6886 

 

e-mail: [email protected] 

Web: www.omega.com

Servicing Mexico and Latin America:

Mexico/

 

 Tel: 001-800-099-0420 (Mexico Only)   

 

Latin America

 

Tel: 001-203-359-7577 

(Outside Mexico) Fax: 001 (203) 968-7290 

 

 

e-mail: [email protected] 

Web: mx.omega.com

Servicing Asia:

China:

 

 Hotline: (+86) 800 819 0559, (+86) 400 619 0559 

e-mail: [email protected] 

Web: cn.omega.com

Servicing Europe:

France:

 

Freephone: 0805 541 038 (France only) 

 

Tel: 01 57 32 48 17 

Fax: 01 57 32 48 18 

 

 

e-mail: [email protected] 

Web: www.omega.fr

Germany/

 

Freephone: 0800 826 6342 (Germany only) 

 

Austria:

 

Tel:+ 49 (0)7056 9398-0 

Fax: +49 (0) 7056 9398-29 

 

 

e-mail: [email protected] 

Web: www.omega.de

Italy

 

Freephone: 800 906 907 (Italy only) 

 

Tel: +39 022 333 1521 

Fax: +39 022 333 1522 

 

e-mail: [email protected] 

Web: it.omega.com

Netherlands:

  Freephone: 0800 099 33 44 (Netherlands only) 

 

Benelux 

Tel: +31 070 770 3815 

FAX: +31 070 770 3816 

 

e-mail: [email protected] 

Web: www.omega.nl

Spain:

 

Freephone: 800 900 532 (Spain only) 

 

Tel: +34 911 776 121 

Fax: +34 911 776 122 

 

e-mail: [email protected] 

Web: es.omega.com

United

 

Freephone: 0800 488 488 (United Kingdom only) 

Kingdom:

 

Tel: +44 (0)161 777 6611 

Fax: +44 (0)161 777 6622 

 

 e-mail: [email protected] 

Web: www.omega.co.uk

It is the policy of OMEGA Engineering, Inc. to comply with all worldwide safety 

and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of 

its products to the European New Approach Directives. OMEGA will add the CE  

mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but 

OMEGA accepts no liability for any errors it contains, and reserves the right to 

alter specifications without notice. 

WARNING: These products are not designed for use in, and should not be used  

for, human applications.

WARRANTY/DISCLAIMER

OMEGA ENGINEErING, INC. warrants this unit to be free of defects 

in materials and workmanship for a period of 

13 months

 from 

date of purchase. OMEGA’s WArrANTY adds an additional one (1) 

month grace period to the normal 

one (1) year product warranty

 

to cover handling and shipping time. This ensures that OMEGA’s 

customers receive maximum coverage on each product. 
If the unit malfunctions, it must be returned to the factory for 

evaluation. OMEGA’s Customer Service Department will issue an 

Authorized return (Ar) number immediately upon phone or written 

request. Upon examination by OMEGA, if the unit is found to be 

defective, it will be repaired or replaced at no charge. OMEGA’s 

WArrANTY does not apply to defects resulting from any action of 

the purchaser, including but not limited to mishandling, improper 

interfacing, operation outside of design limits, improper repair, or 

unauthorized modification. This WArrANTY is VOID if the unit 

shows evidence of having been tampered with or shows evidence of 

having been damaged as a result of excessive corrosion; or current, 

heat, moisture or vibration; improper specification; misapplication; 

misuse or other operating conditions outside of OMEGA’s control. 

Components in which wear is not warranted, include but are not 

limited to contact points, fuses, and triacs.

OMEGA is pleased to offer suggestions on the use of its various 

products. However, OMEGA neither assumes responsibility for 

any omissions or errors nor assumes liability for any damages 

that result from the use if its products in accordance with 

information provided by OMEGA, either verbal or written. 

OMEGA warrants only that the parts manufactured by the 

company will be as specified and free of defects. OMEGA 

MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF 

ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT 

THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING 

ANY WARRANTY OF MERCHANTABILITY AND FITNESS 

FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. 

LIMITATION OF LIABILITY: The remedies of purchaser set forth 

herein are exclusive, and the total liability of OMEGA with 

respect to this order, whether based on contract, warranty, 

negligence, indemnification, strict liability or otherwise, 

shall not exceed the purchase price of the component upon 

which liability is based. In no event shall OMEGA be liable for 

consequential, incidental or special damages. 

CONDITIONS: Equipment sold by OMEGA is not intended to be used, 

nor shall it be used: (1) as a “Basic Component” under 10 CFr 21 (NrC), 

used in or with any nuclear installation or activity; or (2) in medical 

applications or used on humans. Should any Product(s) be used in or 

with any nuclear installation or activity, medical application, used on 

humans, or misused in any way, OMEGA assumes no responsibility 

as set forth in our basic WArrANTY/DISCLAIMEr language, and, 

additionally, purchaser will indemnify OMEGA and hold OMEGA 

harmless from any liability or damage whatsoever arising out of the use 

of the Product(s) in such a manner.

RETURN REQUESTS/INQUIRIES

Direct all warranty and repair requests/inquiries to the OMEGA 

Customer Service Department.  BEFOrE rETUrNING ANY 

PrODUCT(S) TO OMEGA, PUrCHASEr MUST OBTAIN AN 

AUTHOrIZED rETUrN (Ar) NUMBEr FrOM OMEGA’S CUSTOMEr 

SErVICE DEPArTMENT (IN OrDEr TO AVOID PrOCESSING 

DELAYS). The assigned Ar number should then be marked on the 

outside of the return package and on any correspondence.
FOr 

WARRANTY

 rETUrNS, 

please have the following 

information available BEFOrE 

contacting OMEGA:
1. Purchase Order number under 

  which the product was  

 PUrCHASED, 

2. Model and serial number of    

  the product under warranty, and 

3. repair instructions and/or    

  specific problems relative to 

  the product.

FOr 

NON-WARRANTY

 rEPAIrS, 

consult OMEGA for current repair 

charges. Have the following 

information available BEFOrE 

contacting OMEGA:
1.  Purchase Order number to    

  cover the COST of the repair or  

 calibration,

2.  Model and serial number of the 

  product, and 

3.   repair instructions and/or specific 

problems relative to the product.

OMEGA’s policy is to make running changes, not model changes, 

whenever an improvement is possible. This affords our customers 

the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEErING, INC.
© Copyright 2017   OMEGA ENGINEErING, INC. All rights reserved.  

This document may not be copied, photocopied, reproduced, 

translated, or reduced to any electronic medium or machine-readable 

form, in whole or in part, without the prior written consent of OMEGA 

ENGINEErING, INC.

MQS3529/0417

Wiring Connections From Calibrator To PC

For complete product manual:  

www.omega.com/manuals/manualpdf/M3529.pdf

16

15

14

13

13

11

10

9

8

7

6

5

4

3

2

1

BENCHTOP CONTROLLER
INTERNAL WIRING

STEREO JACK  SIDE PANEL

1.8 m (6 ft.)

PC COM PORT

DB–9

1

5

STEREO PLUG –– DB–9

INTERFACE CABLE

CONTROLLER

TX

TX

RX
GND

RX

GRN

Calibrators with the –C2 option come complete with 

communication software, OMEGA part number CN9-

SW. The software is designed to interface with your 

calibrator.

The CN9-SW software is Windows 95/98/NT/2K/

XP compatible.

Cool-Down Procedure

1.  Turn the power switch on the back of the calibrator 

to   “standby” mode. 

2.  The cooling fan may continue to run or turn on 

after several minutes if the heater assembly inside 

the unit has not yet fully cooled down to ambient 

temperature. Do not remove the power cord or 

the main line power until the fan stops running 

permanently.

3.  It is now safe to remove your unit from the power 

source and/or return to storage.

Overheat Reset Switch

If the unit is operated at high temperatures in elevated 

ambient temperatures, an overheat condition may 

occur. In an overheat situation a mechanical reset 

switch on the right side panel will pop and open the 

heater circuit. The controller will still have power. 

While the controller will be demanding heat from the 

heater, the process temperature will fall continuously 

until it equalizes with room temperature. 

If an 

overheat condition occurs, let the unit cool off for one 

hour (leave the unit on), then press the reset button, 

firmly. If this does not correct the problem, contact the 

factory.

OVERHEAT RESET SWITCH

HANDLE (IN RETRACT POSITION)

FRONT

BACK

FAN

NOTE:

Overheat Reset Switch (Right Side Panel)