background image

A

B

A

1
1
1
1

Luminaire
Set of Pictograms
Mounting accessories
Manual

1

2

Pictogram Installation

3

Mounting Methods

2

2

1

1

These  devices  are  used  indoors  and  outdoors                         

o

(ta 40 C) in places where emergency light is needed. 
Each  device  must  be  permanently  connected  to 
mains power supply. In normal operation the battery 
is  charging.  The  light  source  can  be  either  on  or  off, 
depending on user’s choice. In case  of a mains power 
supply  failure,  the  device  enters  emergency  mode 
and  the  illumination  LED  turns  on.  When  the    mains   
power  supply is restored the device turns to normal 
operation.

Autonomy Duration Selection

The  user  can  select  one  of  the  3  available  minimum 
autonomy durations 1 hour, 3 hours and 8 hours. The 
selection  must  be  done  while  the  luminaire  is 
disconnected  from  AC  and  battery  supplies.  The 
selection  is  achieved  through  Switches  2  &  3  of  DS1 
as shown below.

Technical Label Installation

Two  additional  labels  are  included  in  the  package. 
one  for  3  hours  duration  (180)  and  one  for  8  hour 
duration  (480).  Depending  on  the  selected  duration, 
the  installer  must  cover  the  default  1  hour  (60) 
printing  with  one  label  that  has  the  required 
duration. Please take notice of the orientation of the 
label.

Manual Operational Test

Remove  the  diffusor  and  then  by  pressing  the  test 
button briefly an operation test is initiated. The light 
source  and  the  emergency  circuit  of  the  device  are 
tested. The manual test can be conducted only if the 
mains  power  supply  and  the  battery  are  connected. 
During this test period the LAMP TEST LED will  blink. 
The  battery  must  have  adequate  charge.  This  test 
lasts for 3 seconds.

Manual Autonomy Test

A duration test can be conducted by pushing the button 
steadily for 5 to 10 seconds. In order to be performed, 
the mains power supply should be connected and the 
battery should be fully charged. The luminaire enters 
emergency mode, the CHARGE LED is turned OFF and 
the BATTERY FAULT LED starts blinking. Its duration is 
the stated autonomy duration of the luminaire. If at the 
end of the test the autonomy is lower than the nominal, 

the BATTERY FAULT LED will lit and battery needs to be 
replaced.  If  the  result  of  the  test  is  good  then  the 
luminaire enters charging mode and the CHARGE LED 
starts blinking until the battery is fully charged. 

Automatic Operational Test

This test includes all the operations that are provided 
in  Manual  Operational  Test  and  is  conducted 
automatically every 15 days and lasts 3 seconds.
     

Automatic Autonomy Test

The  Automatic  Autonomy  Test  is  conducted  every  6 
months and measures the device’s back up operation 
and  emergency  duration.  This  test  includes  all 
functions of the Manual Autonomy Test.

Wireless communication

The  WL  luminaire  models  have  the  ability  to 
communicate  over  the  air  with  Olympia’s  control 
panels  for  wireless  emergency  luminaires.  The 
luminaires  can  also  communicate  with  a  PC/laptop 
through  a  gateway  (Ethernet,  Wi-Fi,  USB).  For  more 
information,  please  refer  to  Wireless  Emergency 
Lighting guides, available on the company’s website.

Lens Removal

When the luminaire is used without the pictograms or 
the  SP-1100  and  you  require  more  light  output  then 
remove the lens that covers the LEDs.

ΑΤΤΕΝΤΙΟΝ!!!

1.  Operations for installation, maintainance or testing 

must be done by authorized personnel only.

2.   Always use in any case round mains cable, with a 

diameter  of  5-10mm  (H05RN-F  type  2x1mm²  or 
any  other  type,  at  least  equal  to  it’s  mechanical 
and  electrical  properties).  ATTENTION!!  The  cable 
must  not  be  deformed  in  any  way  (This 
requirement is important to ensure the ΙΡ rating).

3.  The device must be connected to the mains power 

supply  through  a  circuit  breaker    that  is  depends 
on the total line’s  power load.

4.  In case of battery replacement, it must be replaced 

by  the  same  type,  by  the  manufacturer  or  a 
competent person.

                

5.  In case of inactive use for a period greater than 2 

months, disconnect the battery by pulling out the 
battery’s connector. 

6. 

I s not allowed to discard batteries into common 

t i

trash  bins,  they  must  be  discarded  only 

in 

battery recycling points. Do not incinerate.

Oly luminaires can be surface mounted on walls or ceilings. For these mounted installations,  special 
accessories are included.

2. Refit the diffusor with the pictogram.

1.  Fit  the  pictogram  you  need  to  the  diffuser,  be  careful  to 
secure it on the 3 plastic holders. 

Wall

bottom

view

Wall installation

Ceiling installation

Ceiling

*  ATTENTION!!!  The  below  mounting  methods  can  be  done  after  request  of  the  necessary 

mounting accessories!!

Extra Mounting Methods *

Suspended ceiling installation 

with mounting accessory

A-3018

Suspended installation with A-3018 accessory

The  luminary  can  be  installed  in  a  suspended 
ceiling.

A marking panel (

SP-1100

) can be installed on the luminary pointing the desired direction.

Suspended ceiling installation 

with mounting accessories  

and marking panel

Ceiling installation 

with marking panel

General

5

6

7

7

8

8

9

NOTE!! 
After  finishing  the  installation  you  must  power  the  luminaire  for  at  least  24  hours  in  order  to 
completely charge the battery. The rated autonomy duration can be achieved after that time.

Package Contents

2

923100402_09_001

923100402_09_001

923100402_09_001

3

4

1h

(default position)

3h

8h

Battery Connection

Attention!!

  The  6  plastic 

latches  (A)  must  be  secured 
(click 

sound). 

This 

requirement  is  important  to 
ensure  the  IP65  rating. 
Power on the luminary.

ON

1 2 3 4

ON

1 2 3 4

ON

1 2 3 4

6) Autonomy Duration Selection

(Read on General Informations, Page 1)

7 a) Pernament Maintained Operation

7 b) Non-Maintained Operation

7 c) Controlled Maintained Operation of the lamp

ON

1 2 3 4

11

10

WARNING!!

 Isolate the mains power supply before making the connections.

Ν

 for neutral, 

L

 for live wire

Ν

 for neutral, 

L

 for live wire

 WARNING!!

 Isolate the mains power supply before making the connections.

Description

Indications LED Status

BATT.

FAULT

(yellow)

LAMP
FAULT

(red)

CHARGE

(green)

Fully charged

Charging

Battery fault or
emergency mode

Operational test

Light source fault

Autonomy test

Duration fault

Note:

Permanently

ON

Blink

Indifferent

Off

N
L

Link

N
L

1

Installation Instructions

or

Switch number 4 of DS1 
must be in ON position. 

ON

1 2 3 4

Switch number 4 of DS1 
must be in OFF position. 

and

ON

1 2 3 4

Switch number 4 of DS1 
must be in OFF position. 

and

N
L

External

switch

1

2

3

4

5

Drill  one  of  the  5  available  holes  with  a  16-18mm  drill  bit.  Install  the  included  rubber  gasket  and  pass 
through the power cables. Install the included tie (if needed) to fasten and securely the power cables. 

1

2

Reviews: