Thank you for purchasing this product of Olympia
Electronics. A European manufacturer.
GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each luminaire
must be permanently connected to mains power
supply. In normal operation the led strip lights and
the battery is charging. In case of a mains power
supply failure the luminaire will light the led strip
automatically in emergency mode. When the mains
power supply is restored the device turns to
normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2.
OPERATION
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire enters
the idle state and battery consumption is negligible,
in order to be protected from deep discharge.
Battery charging
The battery charging is completely controlled. In this
case, is achieved the perfect battery maintenance ,
as well as the elongation of its duration. When the
battery has completely charged, it charges with a
maintenance current.
Manual Test
The manual test can be conducted only if the main
power supply and the battery is connected. By
pressing the TEST/RESET button briefly (page 2)
an operation test is initiated. During this test period
all indication LEDs are OFF.
Automatic test
This test includes all the operations that provide the
manual test and is conducted automatically
every 15 days. In order to be performed, the main
power supply and the battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted and
measures the luminaire`s back up operation. This
test is conducted automatically every six months. In
order to be performed, the main power supply and
the battery should be connected (the battery should
be charged). If the battery is not charged, the test is
postponed until the battery is completely charged. If
during
the
Automatic
Autonomous
Test
the
luminaire’s duration is lower than the named, then
the battery must be replaced.
Back Up Operation
The
autonomous
duration
of
battery
during
emergency mode is at least the one that is stated in
the technical characteristics. During emergency
mode, a LED strip test is also performed.
Resetting Errors
Push the TEST/RESET button for 5 seconds, to
extinguish all the indicated LED errors (page 2).
Then the luminaire enters regular operation mode.
Indication LED status
(with connected mains power supply).
Charge
On:
Good charge current.
Οff:
No battery (No charging current or
disconnected battery).
Lamp fault
Οn:
faulty LED strip.
Off:
Good LED strip.
Fault
Οff:
Battery OK.
Blink
(With
Charge LED
ON): Autonomy or low
battery problem
(the battery must be replaced).
Blink
(With
Charge LED
Off):
No charging current or disconnected battery.
Page 1 from 2
923940000_09_008
High Quality European based Manufacturers
GR-940/15L WATERPROOF SELF-TESTING EMERGENCY LUMINAIRES
220-240V AC/50-60Hz
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
CHARGING TIME
INDICATIONS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (MAINS / EMERGENCY)
ILLUMINATION SOURCE
24h
Charge, lamp fault, fault indication LED
From overcharge and full discharge
IP 65
3.6V/3Ah
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
0 to 40 C
o
Up to 95%
3 years (1 year for the battery)
105lm / 105lm
480min
15 white LED’s
4W/7VA
945gr.
363 x 145 x 73 mm