GENERAL

These  luminaires,  according  to  Lloyd’s 
Register  Type  Approval  System  are 
s u i t a b l e   f o r   m a r i n e   a n d   o f f s h o r e  
applications  for  use  in  environmental 
categories ENV1, ENV2, ENV3 and ENV4, 
where  ENV1  are  controlled  environments, 
ENV2  are  enclosed  spaces  subject  to 
temperature, humidity and vibration, ENV3 
are enclosed spaces subject to generated 
heat  from  other  equipment  and  ENV4  are 
mounted on reciprocating machinery. Each 
luminaire  must  be  permanently  connected 
t o   m a i n s   p o w e r   s u p p l y

.

  I n   n o r m a l  

operation  the  led  strip  lights  and  the 
battery is charging. In  case  of  a  mains  
power    supply  failure    the    luminaire    will   
light  the  led  strip    automatically  in 
emergency  mode.  When  the    mains   
power    supply    is    restored  the  device 
turns to normal operation. 

INSTALLATION

To  install  the  luminaire  follow  the 
installation instructions on page 3.

OPERATION
Battery charging

The  battery  charging  is  completely 

controlled

In  this  case,  is

 

achieved  the 

perfect battery maintenance 

as well as the 

elongation of its duration

When the battery 

has  completely  charged

it  charges  with  a 

maintenance current.

Battery Cut-off

The luminaire enters in this operation when 
the  mains  power  supply  fails

 

and  battery 

has  lost  its  energy

During  this  operation 

the  luminaire  enters  the  idle  state

 

and 

battery  consumption  is  negligible,  in  order 
to be protected from deep discharge.

Manual

 Test

The  manual  test  can  be  conducted  only  if 
the  main  power  supply  and  the  battery  is 
connected.  By  pressing  the  TEST/RESET 
button  briefly  (page  3)  an  operation  test  is 
initiated.  During  this  test  period  all 
indication LEDs are OFF.

Automatic Test

This  test  includes  all  the  operations  that 
provide  the  manual  test  and  is  conducted 
automatically every 15 days. In order to be 
performed,  the  main  power  supply  and  the 
battery should be connected. 

Automatic Autonomous Test

The 

Automatic 

Autonomous 

Test 

is 

conducted  and  measures  the  luminaire`s 
back  up  operation.  This  test  is  conducted 
automatically  every  six  months

In  order  to 

be performed, the main power supply and 

                       WATERPROOF SELF TESTING EMERGENCY LUMINAIRES

 

Page

 1

 from

 2

220-240V AC/50-60Hz

Bayblend FR3010

transparent 

 

polycarbonate

TECHNICAL CHARACTERISTICS

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)

CHARGING TIME

INDICATIONS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION

PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

24h

Charge, lamp fault, battery fault indication LED

From overcharge and full discharge

IP 65

3.6V/3Ah

  210lm / 210lm 

o

5 to 40  C

Up to 95% 

3 years 

(1 

year for the battery

)

940gr.

363 x 145 x 73 mm

  105lm / 105lm 

180min

5W /8.5VA

3.5W / 7.5VA

3.6V/1.5Ah

  30 white LED’s 

  15 white LED’s 

GR-939/15L/MAR

GR-939/30L/MAR

870gr.

923939017_09_003

High Quality European based Manufacturers

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

, IEC 60092-306, IEC 60533