GENERAL
This luminaire is used in places where
emergency luminaires are needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply
.
In normal operation the led strip lights and the
capacitor is charging.
In case of a mains power supply failure the
luminaire will light the led strip automatically
in emergency mode. When the mains power
supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
Capacitor charging
The capacitor charging is completely and
accurately controlled
.
In this case, is
achieved
the perfect capacitor maintenance
,
as well as
the elongation of its duration
.
When the
capacitor has completely charged
,
it charges
with a maintenance current.
Capacitor Cut-off
The luminaire enters in this operation when the
mains power supply fails
and capacitor has lost
its energy
.
During this operation the luminaire
enters the idle state
and the capacitor’s
consumption is negligible.
Manual
Test
The manual test can be conducted only if the
main power supply and the capacitor is
connected. By pressing the TEST/RESET
button briefly (page 3) an emergency operation
test is initiated. During this test period all
indication LEDs are OFF and the whole
emergency circuit is monitored.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
main power supply and the capacitor should be
connected.
Manual Autonomous Test
If the Test button is pressed for a period
between 5 to 10 seconds (with the capacitor
fully charged), the illumination sign will enter in
counting autonomy condition.
If the capacitor is
not fully charged this command is ignored
.
The BAT FAULT LED blinks during the
measurement, indicating this process to the
user. This measurement duration is equal with
the nominal autonomous duration of the
luminaire and at the end of the process, if the
measured duration was at least the nominal
autonomous duration, the BAT FAULT LED is
turned
OFF,
in
the
other
hand
stays
continuously ON indicating to the user that the
capacitor must be replaced.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the luminaire’s sign’s back up
operation and emergency duration. This test is
conducted automatically every six months
.
In
order to be performed, the main power supply
Page
1
from
4
GR-900/30L/SC
Waterproof Self Testing Maintained Emergency Luminaire
220-240V AC/50-60Hz
TECHNICAL CHARACTERISTICS
(for LED module specifications see page 4)
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS (L x W x H)
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BACK UP SOURCE
CHARGING TIME
INDICATIONS - CONTROLS
CAPACITOR PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
LIGHT SOURCE INTENSITY
ILLUMINATION SOURCE
3h
CHARGE, LAMP FAULT, BAT FAULT
,
TEST button
From overcharge
o
-40 to 65 C
Up to 95%
10 years
363 x 145 x 73 mm
White LEDs
6W / 6.5VA /PF: 0.92
IP65
60 min
250lm (230V AC) / 90lm (emergency)
1012gr.
Super Capacitor A-900/SC
Page
4 from
4
Important notice for the installed luminaires in one area !!!
The installer must connect the capacitor’s connector first and then should power the luminaire.
The capacitor connection must have at least a time variation of 1.5 minute for each luminaire.
With this variation, it is ensured that the non synchronized Automatic Autonomous Test for two or
more luminaires installed in one area, is not conducted in the same day.
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Super capacitor replacement
(Α-900
/SC
)
It can be done only by a competent person and after
the mains interruption
1.
Unfasten the 4 screws (step 8 page 3) and remove the
diffuser
.
Unfasten the 2 retaining screws and remove the
reflector (step 7 page 3).
2. Disconnect the connector and remove the old
capacitor
pack by untastening the retaining screws .
3. Connect the new
capacitor pack (step 4
of the installation
procedure
)
place it in the position
of the old one
and fasten the removed screws
.
4.
Refit the removed parts in previous steps
and power the
device.
s
Thank you for your trust in our products
Olympia Electronics - European manufacturer
(*)
Maintained operation: The luminaire lights its
illumination source, when it is powered by the mains
power supply or not
.
Non Maintained operation: The luminaire lights its
illumination source,
only in power supply’s failure.
Note!! T
he installer should fill in
, on the specification
label,
the letter
G
if the luminaire is used as a safety
sign
.
NOTE:
LED= Light Emitting Diode
LABELING EXPLANATION:
X:
Self contained
1:
Maintained
(*)
A:
Including test device
G:
Internally illuminated safety sign
60:
1 hour duration
The light source contained in this luminaire shall only be replaced by the manufacturer, or his
agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of
warranty is specified in the official catalogue of Olympia Electronics and also in the technical leaflet,
which accompanies each product. This warranty ceases to exist if the buyer does not follow the
technical instructions included in official documents given by Olympia Electronics or if the buyer
modifies the goods provided or has any repairs or re-setting done by a third party, unless Olympia
Electronics has fully agreed to them in writing.
Products that have been damaged can be returned to
the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge
the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or
not the buyer the transportation cost.
HEAD OFFICE
72
nd
km
.
O
.
N
.
R
.
Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
[email protected]
LED MODULE CHARACTERISTICS
Manufacturer
Model Number
Voltage Range
Connections
Nominal Power
Temperature (tc)
Olympia Electronics S.A.
45 °C max. across the board
Cable connection with non reversible connectors
17.4-21.6V DC
2W
GR-900/30L/SC
1505153
923900000_09_010
923900000_09_010
X
1
6
0
A
G
S
S