background image

Page 1 from 5

923578007_09_003

GENERAL

These  luminaires  are  used  in  places  where 
emergency luminaires are needed. 
E a c h   l u m i n a i r e   m u s t   b e   p e r m a n e n t l y  
connected  to  mains  power  supply.  In  normal 
operation  (L1  connected  to  L)  the  led  strip 
lights  and  the  battery  is  charging.  In    case    of   
a mains power supply failure the luminaire  will 
light  the  led  strip  automatically  in  emergency 
mode  (powered  by  its  battery).  When  the 
mains  power  supply  is  restored  the  device 
turns to normal operation. 

OPERATION
Battery Charging

The  battery  charging  is  completely  controlled. 
In  this  case,  the  best  possible    battery 
maintenance  is  achieved,  as  well  as  the 
elongation  of  its  duration.  When  the  battery 
has  completely  charged,  it  charges  with  a 
maintenance current.

Battery Cut-off

The  luminaire  enters  in  this  operation  when 
the  mains  power  supply  fails  and  battery  has 
lost  its  energy.  During  this  operation  the 
luminaire  enters  the  idle  state  and  battery 
consumption  is  negligible,  in  order  to  be 
protected from deep discharge.

Manual Test

This  test  can  be  done  by  placing  the  test  card 
on  the  side  of  the  indications  (page  4)    and 
remove it instantly an operation test is initiated. 
The  light  source  and  the  emergency  circuit  of 
the  device  is  monitored.  The  manual  test  can 
be  conducted  only  if  the  mains  power  supply 
and  the  battery  is  connected.  During  this  test 
period all indication LEDs are OFF. 

Automatic Operational Test

This test includes all the operations that provide 
the manual test and is conducted automatically 
every  15  days.  In  order  to  be  performed,  the 
mains  power  supply  and  the  battery  should  be 
connected. 

Automatic Autonomous Test

The  Automatic  Autonomous  Test  is  conducted 
and  measures  the  device’s  back  up  operation 
and emergency duration. This test is conducted 
automatically  every  6  months.  In  order  to  be 
performed,  the  mains  power  supply  and  the 
battery should be connected and fully charged. 
If  the  battery  is  not  fully  charged,  the  test  is 
postponed  until  the  battery  is  completely 
charged. If during this test, the autonomy is less 
than  nominal  then  the  battery  fault  led  turned 
on  continuously  and  the  battery  must  be 

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

WATERPROOF SELF TESTING MAINTAINED 

EMERGENCY LUMINAIRE

 GR-578/L/18/ST/WP

220-240V AC/50-60Hz

180 min

10640gr (double side)

OPERATION TEMPERATURE RANGE

RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd) 

 

 

CHARGING TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

LIGHT SOURCE INTENSITY (230V AC/emerg.)

ILLUMINATION SOURCE

24 h

Charge LED, Lamp Fault LED, Battery LED

From overcharge and deep discharge

  White LEDs

5 to 40  C

o

Up to 95% 

3 years (1 year for the battery)

Painted steel plate (RAL 7036), Bayblend FR3010, transparent  polycarbonate

IP65

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838

635 x 635 x 105 mm

4.8V/3Ah

12W / 12.5VA - PF: 0.95/230V for luminaire

  

/ 425lm 

 850lm 

TECHNICAL CHARACTERISTICS 

(

for LED MODULE Specs. see page 5

)