921802003_09_005
Page 1 from 9
BSR-8020/WP/MAR
Waterproof addressable input-output unit
ON
OFF
GENERAL
The input-output unit is used in ships. It is recognized and programmed by the BSR-2100 panel. This device is used to
connect to the loop non-addressable devices that have a free relay contact (such as fire alarm panels, flow switches and
conventional detectors). The input unit is fully monitored and can send to the panel, with a suitable connection, three states:
quiescent, fault, alarm. The output unit contains a fully programmable by the panel relay with a rating of (30V/1A).
The red LED that blinks periodically in the quiescent state is an indication of power and good operation. The LED lights and
remains lit when the specific input unit issues an alarm to the panel. The LED also remains lit if the sirens are deactivated
from the panel in order to show the precise point where the alarm originated from. The Led is turned OFF after a panel
reset. Each device must have an address, that is recognized by the panel. It is not allowed for two devices on the same
loop to have the same address. Page 4 contain the full table that shows the addresses and how they can be set with the
micro switches. Up to 127 units can connected to each panel.
INSTALLATION
(
Notice!!! The mounting accessories are included
)
1. Unfasten the front cover screws and remove the cover.
2. Locate the mounting holes and use the supplied accessories to mount the unit on the required position.
3. Pass the cables through the cable glands and make the required connections.
4. Notice!! If an additional entry hole is required then remove the break-out plastic and install the supplied cable gland.
5. Set the address on the dip-switch (page 4 and 5).
6. Reinstall the front cover and fasten the screws that were removed in step 1.
21-28V
Bayblend FR3010
ALARM CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER
QUIESCENT CONSUMPTION WHEN USED AS A CONVENTIONAL DEVICE DRIVER
30mA
5.6mA
IP65
1.3mA (with activated LED)
o
-10 to 60 C
Up to 95%
2 years
170gr.
155x80x43mm
EN 54-18, IEC 60092-504, IEC 60533
Technical characteristics
RELATIVE HUMIDITY
CONSTRUCTIONAL MATERIAL
WEIGHT
DIMENSIONS
GUARANTEE
OPERATION VOLTAGE
QUIESCENT CONSUMPTION
ALARM CONSUMPTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
DEGREES OF COVER PROTECTION
0.7mA
INSTALLATION
EXTERNAL POWER SUPPLY
For internal use only
21-28V
Thank you for your trust in our products
Olympia Electronics - European manufacturer
Indicator LED
1
2
2
3
3
5
4