GENERAL
This device is used as an indication of a fire panel
that sounds a warning signal from the siren and
provides visual indication using the beacon. The
sound level and the luminous signal it produces
covers an area of several square meters. It is
compatible with fire panels that support Olympia A
Protocol.
CONNECTION AND MOUNTING
1.
Unscrew the screw and remove the plastic
cover using a flat screwdriver to the point under
the screw (Picture
1
page
2)
.
2.
Unscrew the four screws and detach the plastic
from the base (Picture 2).
3.
Drill the holes needed to pass the connection
cables. Place the cable glands and open a hole to
the center with a small screwdriver. Pass the
connection cables through the glands of the device
(Picture 3).
4.
Use the supplied mounting materials to place the
base of the siren in height up to 2.4 meters from the
gound (Figure 1 page 2). Install the plastic plugs and
fasten the screws in the mounting holes.
CAUTION!!
Make sure that the base of the siren is installed in the
correct orientation.
5
.
To
adjust the type of the sound indication
use
the DIP switches 1 to 5, according to Table 1 (page 4).
6.
To
adjust the sound level
use the DIP switches 6
to 7, according to Table 2 (page 5).
7.
To
adjust the frequency of the flashing LED
use
DIP switch 8 according to Table 3 (page 5).
8.
Refit the plastic and fasten the 4 screws you
removed in step 2.
9.
Refit the plastic cover and fasten the screw.
10.
Test the operation of the device through the panel
after the installation.
The BSR-5132/WP integrates an isolator short circuit
which activates automatically by disconnecting the
defective node from the loop and allowing it’s
detection though the panel.
MAXIMUM SOUND LEVEL IN 1 METER
ENVIROMENTAL TYPE
MOUNTING
COVER (y)
BEACON
11
-
30
V DC
Type
Β
1 power
LED
Wall mounted (W)
1A
5
A
50mΩ
6
meters
in the peripheral of the beacon with
180°
angle
101
dB
90μΑ
7
.
4
to
35
.
9
m
Α
IP65
COVER AREA
FLASHING RATE
FLASHING COLOUR
86
.
4m³
maximun
Adjustable to 1 Hz or 0.5 Hz
Red
EN 54-3,
ΕΝ-54-17,
EN 54-23
o
-25
to
70
C
Up to 95%
2 years
313
gr.
127x137x82 mm
ABS/PC,PC
MOUNTING HEIGHT (x)
2
.
4
meters max
COVER AREA CODE
W-2,4-6
10.7 - 12.7
9.3 - 10.6
Waterproof addressable sounder with beacon
and integrated isolator
Β
SR-5132
/
WP
Page
1 from
5
921513201_09_001
TECHNICAL CHARACTERISTICS
Thank you for your trust in our products
Olympia Electronics - European manufacturer
MAIN VOLTAGE
STANDBY CONSUMPTION
ALARM CONSUMPTION
2
5mA pulses (6ms duration every
2
sec)
GUARANTEE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
ISOLATION VOLTAGE
(
Vso min-max
)
RECONNECT VOLTAGE
(
Vsc min-max
)
MAXIMUM SERIES RESISTANCE
(
Zc max, -L in-out
)
MAXIMUM LEAKAGE CURRENT IN ISOLATION MODE
(
I max, -L in/out
)
L
MAXIMUM LOOP CURRENT
(
Ic max, -L in/out)
MAXIMUM SWITCH CURRENT
(
Is max, -L in/out)
COMMUNICATION PROTOCOL
Olympia A Protocol