GENERAL
This device is used as an audible warning sounder
in case of fire event
.
The sound level covers an
area of several square meters. It is compatible
with fire panels that support Olympia A Protocol.
CONNECTION AND MOUNTING
3.
Drill the holes needed to pass the connection
cables. Place the cable glands and open a hole to
the center with a small screwdriver. Pass the
connection cables through the glands of the device
(Picture 3).
1.
Unscrew the screw and remove the plastic
cover using a flat screwdriver to the point under
the screw (Picture
1
page
2)
.
4.
Use the supplied mounting accessories to place
the base of the siren in height up to 2.4 meters from
the gound (Picture 3 page 2). Install the plastic
plugs and fasten the screws (with the supplied
rubber sealing ring and washer) in the mounting
holes.
CAUTION!!
Make sure that the base of the
siren is installed in the correct orientation.
2.
Unscrew the four screws and detach the plastic
from the base (Picture 2).
6.
To
adjust the sound level
use the DIP switches 6
to 7, according to Table 2 (page 6).
The BSR-51
30
/WP integrates an isolator short circuit
which activates automatically by disconnecting the
defective node from the loop and allowing it’s
detection though the panel.
9.
Test the operation of the device through the panel
after the installation.
7.
Refit the plastic and fasten the 4 screws you
removed in step 2.
5
.
To
adjust the type of the sound indication
use
the DIP switches 1 to 5, according to Table 1 (page 4).
8.
Refit the plastic cover and fasten the screw.
MAXIMUM SOUND LEVEL IN 1 METER
ENVIRONMENTAL TYPE
MOUNTING
1
2-
30
V DC
Type
Β
Wall mounted
1A
5
A
300
mΩ
101
dB
90μΑ
7
.
4
to
35
.
9
m
Α
IP65
COVER AREA
26.5
m³
maximun
EN 54-3:2001,
ΕΝ-54-17
:2005
o
-25
to
70
C
Up to 95%
2 years
313
gr.
127x137x82 mm
ABS/PC,PC
MOUNTING HEIGHT (x)
2
.3
meters max
COVER AREA CODE
O-2,3-2,4-4,8
10.2 - 13
8.8 - 11
WATERPROOF ADDRESSABLE SOUNDER WITH INTEGRATED ISOLATOR
Β
SR-5130
/
WP
Page
1 from
6
921513000_09_003
TECHNICAL CHARACTERISTICS
Thank you for your trust in our products
Olympia Electronics - European manufacturer
MAIN VOLTAGE
STANDBY CONSUMPTION
ALARM CONSUMPTION
2
5mA pulses (6ms duration every
2
sec)
GUARANTEE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
ISOLATION VOLTAGE
(
Vso min-max
)
RECONNECT VOLTAGE
(
Vsc min-max
)
MAXIMUM SERIES RESISTANCE
(
Zc max, -L in-out
)
MAXIMUM LEAKAGE CURRENT IN ISOLATION MODE
(
I max, -L in/out
)
L
MAXIMUM LOOP CURRENT
(
Ic max, -L in/out)
MAXIMUM SWITCH CURRENT
(
Is max, -L in/out)
COMMUNICATION PROTOCOL
Olympia A Protocol
21
1293