1503600-009-001
1503600.009-001
BSR-5036
Addressable manual call point
24 / 07 / 2003
24 / 07 / 2003
Technical Specifications
Main voltage
Standby consumption
Alarm consumption
Degrees of cover
Produced in accordance with
Operation temperature range
Humidity
Dimensions
Weight
Guarantee
14-30 V
1 mÁ
1.5 mA (
with activation
LED)
IP 20
EN 54
o
-20
60 C
to
Up to 95% relative humidity
100 x 100 x 60 mm
200 gr
2 years
Description
BSR-5036 is a addressable manual call point which activates the fire detection
panel. It is essential for it to exist in co-operation with the detectors. At least one
button has to be placed in every fire detection system, near to the main control
panel. Pushing the clear plastic cover, the button activates the alarm system. The
clear plastic cover does not brake but can be reset to it
’
s original position with the
special plastic key which is included in the package. With this way you can test a
specific button as well maintenance the fire detection panel.
It is mounted in a clearly visible spot, near at exit or ladder and at a height of 1,5
metres.
A red coloured LED that blinks periodically in standby detection mode, is a power
indication LED and indicator for the good operation of the device. When a button
issues an alarm the LED lights. When we sillence the sirens the LED remains lit to
show us the detector that issued the alarm.
The LED goes off when we RESET the panel.
Each button has an address with which it is recognized from the panel.
It
’
s forbidden for two devices with same addresses to be connect to the same loop.
The back page contains all the available address settings which are done using the
dipswitch.
The panel references the buttons with the name
‘’
CALL POINTS
‘’
+L -L +L -L
A
P
1
2
3
4
5
6
7
8
O
N
Indicator LED
.
Blinks periodically in standby detection mode.
The LED light when a button issue an alarm.
The LED goes off when we RESET the panel
Select the signal that the button sends to the panel.
In position (Á)
the button sends an alarm signal.
In position (Ñ) the button sends a prealarm signal .
(We have to also programm the pane
l
)
Address selection dipswitches .
Åach device has its own address.
Terminal block for connecting to the loop.
+
L
-L
+
L
-L
A
P
1
2
3
4
5
6
7
8
ON
+
L
-L
+
L
-L
A
P
1
2
3
4
5
6
7
8
ON
Loop
Loop
Loop
Loop
IN
IN
O
U
T
OU
T
R
IN
IN
O
U
T
OU
T
R
IN
IN
O
U
T
OU
T
R
IN
IN
O
U
T
OU
T
R
IN
IN
O
U
T
OU
T
R