background image

Page 1 from 5

SOUNDER WITH BEACON FOR FIRE DETECTION PANEL

GENERAL

This device is Visual Alarm Devices (VAD) for 
fire detection panels that offer a strong sound 
output  and an optical warning with a  beacon 
and is used on ships. The strong sound and 
the  optical  warning  beacon  cover  many 
square metres.

 It features two inputs (N1, N2) 

for  the  production  of  two  different  sounds.

 

 

This  device  can  co-operate  with  any  fire 
detection  panel  (BSR-2104/MAR,  BSR-
2114/MAR, BS-1632, BS-1634, BS-1636, BS-
636).

Installation and Connection
1.

 First, remove the retaining screw, place a

    flat blade screwdriver in the holes  of the
    plastic hooks and remove the plastic cover
    (Image 1 on page 2).

 

2.

 Remove carefully the beacon connector

    (Image 2 on page 2).

3.

 Use the supplied mounting parts to install the

    siren’s base at a  height of  2.4 metres from
    the floor (figure 1 on page 2). Place the
    plastic plugs and fasten the screws to the
    mounting holes

.

 Attention!! Make sure that

    the siren’s base is installed upwards 

as

    

shown in figure on page 4.

4. 

Place the caps and make a hole in the center

    

using a small screwdriver.

 

Pass through the

    caps the cables to connect the device.

 

5.

 

The (

+N1

 

or the 

+N2

)

 

terminal block

 is

 

    connected to the

 (

+

)

 

output of

 

Alarm-1

 

or

   

 Alarm-2

 

of the panel and the (

-

)

 

of the

    terminal block is connected to the

 (

-

)

 out

put

    of 

Alarm-1

 or 

Alarm-2

 

of the panel.

    Accordingly connect in parallel all the sirens.
    (The maximum number of sirens depends on
    the  type  of the  panel). 

6

.

 

To select various

 

sound effects

 use the

    dipswitch 1,

 

2

 and 

3 and

 choose the

    

diserable sound effect,

 

according to

 tables 2

    and 3 on page 3. 

7

.

 

For 

LED effect 

variation use the dipswitch 4

    (Table 1) on page 2. On the last siren of the
    line, we must connect in parallel with its
    power cables, the terminal resistor that was
    removed from the alarm contacts of the 
    panel.

 

8.

 

Reinstall the beacon connector (step 2).

    Refit the plastic cover until the plastic hooks
    are securely attached (step 1) and fasten the
    retaining screw (torque 0.6Nm). Attention!!
    Make sure that the siren’s cover is installed

    in the correct orientation.

9.

 Test the device after installation.

 

Β

S-531

/1

/MAR

ΤΕCHNICAL CHARACTERISTICS

OPERATION VOLTAGE
MAXIMUM CONSUMPTION
MAXIMUM SOUND OUTPUT in1m

ΤYPE OF APPLICATION ENVIRONMENT

MOUNTING
COVERAGE (y)

BEACON

21-28V DC

Τ

ype

 Α

1 Power LED

Wall

6 m around the siren at an angle of 180°

94dB (sound effect 1

)

1.2W

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS

TYPICAL WEIGHT 
GUARANTEE

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

IP 42C

COVERAGE VOLUME 
FLASH RATE
FLASH COLOUR

86.4m³

 

(max) 

1 Hz (Switchable to 0.5 Hz)

Red

o

0 to 60  C

Up to 95% 

2 years

230gr.

141 x 141 x 100 mm

CONSTRUCTION MATERIAL

Bayblend FR3010

transparent

 

polycarbonate

MOUNTING HEIGHT (x)

2.4m max

COVERAGE VOLUME CODE

W-2.4-6

921531009_09_0

0

4

Thank you for your trust in our products 

Olympia Electronics -  European manufacturer

rd

EN 54-3:2001+A1:2002+A2:2006, EN 54-23:2010, EN 50130-4:2011, IEC 60092-504

 3

 Ed.:2001+Cor1:2011, IEC 60533:1999 Edition 2.0

Reviews: