Bi2 WALL AR 1000/1200/1400
EN - 23
ENGLISH
Led status
Mode of operation
Off
Board in Stand-by (contact CV open)
On
Board on (contact CV closed)
1 Blink
Temperature H2O > 20°C in summer mode or
Temperature H2O < 30°C in winter mode
2 Blinks
Motor locked/disconnected or safety grille open
3 Blinks
Water temperature sensor open or short circuited
4 Blinks
THIS SIGNAL IS NOT AN ALARM
At every start-up, the system checks the software version of the
power board
5 Blinks
The motor feedback indicates a speed > 1400 rpm
6 Blinks
The motor feedback indicates a speed < 100 rpm
(see locked fan function)
5.1 - HOT/COLD GENERATOR SWITCHING ON CONSENT CONTACT
The screw connector (C) on the black and grey cables of the thermoelectric head is a
free contact (closed = valve open, 230 V max, 1 A max) to give consent for switching
on of the hot/cold generator.
5.2 - CONFIGURATION
Disconnect power feeding from the board before config
J1 - MOUNT
ON: Installation of the high wall unit.
OFF: Not used.
J2 - SEL1 and J3 - SEL2
SEL1
SEL2
OFF
OFF
Not used
OFF
ON
Not used
ON
OFF
Units with Flap
ON
ON
Not used
Only at first start-up of the board, for approximately 3 seconds, the relay of the
valve carries out a series of commutations to confirm the selected configuration.
Once the operations have been completed, reposition the previously disassembled
parts taking care to connect the earth connection cable. Secure the front panel by
means of the screws, then power the machine.
Summary of Contents for Bi2 WALL AR 1000
Page 2: ......
Page 207: ...Bi2 WALL AR 1000 1200 1400 EL 3 0 0 1 0 2...
Page 208: ...EL 4 0 3 1 2 3 4 5 6 7 8...
Page 209: ...Bi2 WALL AR 1000 1200 1400 EL 5 0 4 1 2 3 4 5 2 21m 6 7 8 9...
Page 210: ...EL 6 10 11 12 13 3mm 14 3 C 70 C PH 6 5 7 5 15 16 17 18 19 20 21 22...
Page 211: ...Bi2 WALL AR 1000 1200 1400 EL 7 23 24 25 26 27 28 29 30 1 2 3 4 5...
Page 212: ...EL 8 6 1 1 7 8 9 10 11 12 13 14 80 15 16 17...
Page 213: ...Bi2 WALL AR 1000 1200 1400 EL 9 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32...
Page 214: ...EL 10 0 5 1 2 3 4 5 0 6 fancoil fancoil 1 2 0 7 fan coil...
Page 217: ...Bi2 WALL AR 1000 1200 1400 EL 13 e f g h i 3 3 1 a b c 3 2 3 2 1...
Page 220: ...1 1a 1a 1 9 X Y 8 EL 16 c 1a 1 3 2 4 8 9 a 4 X b 2 Y...
Page 221: ...Bi2 WALL AR 1000 1200 1400 A A 1a A 1 1a V V 10 EL 17 3 2 5 10 a 1 1 b c V...
Page 224: ...3a 3b 3a 3 3b 3 3a 3a 14 EL 20 5 0 5mm2 20 20mm 3a 3b 3 14 30 mA CEIEN 3mm...
Page 228: ...EL 24 fan coil 6 3 C 20 C 30 C 70 C Max 10bar Min 1 5 bar 7 8...
Page 230: ...EL 26 d 7 e 7 f 7 g 7 8 2 a b c d e a b 9 a b c 9 1 a 5 LED 6...
Page 231: ...Bi2 WALL AR 1000 1200 1400 EL 27 b 20 10 c 5 LED 2 9 2 a b a a 9 3...
Page 232: ...EL 28 7 C AUTO TEMP FAN...
Page 317: ...26A00055A 2...