background image

18 

IMTP 2.2 - ITTP 2.2/4/5.5/7.5 

    

ENG

 

 

The Inverter stop the motor for 
Minimum Flow with a high flow 
condition and then re-start and 
stop again, continuously 

A small water membrane Tank charged with 1.5-2 Bar air pressure is required for a 
correct working; check it. 
The condition may also caused by a not correct pump curve saving during the 
automatic check: possibly the delivery was not totally closed and the Inverter checked 
a higher curve of the pump; repeat  the automatic check (Pump data -> check ON, 
then exit to the menu and press START) closing totally the outlet and try again the 
functioning. 
Verify if there is a no-return inlet valve on the pump and if itÕs working good without 
loses. 
ItÕs possible to reduce the flow before stopping reducing the parameter F1 
ItÕs possible to reduce the flow before stopping reducing the parameter Minimum Flow 
Power stop % on Motor Data. 

The inverter donÕt switch off the 
pump when the valve on 
delivery is totally closed 
 

Probably check was done with pump not perfectly filled up; remake the check 
procedure after a complete filling of the pump and try again if pump switch off correctly 
in minimum flow condition. If the problem remain, try to grow up the function: 
Advanced Functions -> Motor data -> Minimum flow power stop, upgrading 2% every 
time and testing pump, till find the correct working. 

10 

The hydraulic system have a big 
tank (>40 l) and, after check did 
correctly with closed delivery, 
the pump stop for minimum flow 
with a high flow, and then re-
start and stop again, 
continuously 

Probably during the automatic check there was a flow of water to full up the big tank, 
for that the pump curve saved by the inverter is not the correct curve (with null flow 
and maximum pressure).  
Maintain full of water the tank (pressure near maximum value); repeat the automatic 
check (Pump data -> check ON, then exit to the menu and press START). When the 
check finish try to work again testing the minimum flow stop condition of the motor that 
must be with a small flow. 

11 

The Inverter stop the motor for 
Dry Working condition  

Sometimes the problem is caused by the same Automatic Check error that previous 
point (see possible solution like above). 
In other cases possibly there is air mixed with the water on the inlet of the pump 
(verify pipes and junctions). 

12 

The pump donÕt switch off for dry 
working when the inlet pipe and 
the pump are empty 
 
 

In normal working condition, with pump and pipes filled up, remake a check procedure 
(Pump data -> Check=ON) and try again. If the problem remain grow up the 
parameter: Motor Data -> Dry Working power stop, from 80% default value doing 10% 
steps, testing every time the pump. If the problem cannot disappear also with Dry 
working power stop more than 100%, verify that pump havenÕt any defect (fault seal, 
impellers, etc) that can cause a big power absorbing also without water, in dry 
condition. 

13 

A group of two or more inverters 
cannot communicate between 
each other in Master-Slave 
mode 

For the BC inverters type read on left. 
For the RS type check the correct connection RS485 by a two wires cable (A to A and 
B to B). 
Verify the communication set to Master-Slave on Advanced Functions -> Group 
Functioning (code 0 for the inverter Master, code 1, 2, etc for all the others Inverters 
Slave) 

14 

The Inverter conduct on the 
input voltage supply line 
electromagnetic noises that 
disturb other electronic devices 

Check Ground cable connections (Ground system must be radial type, with resistance 
less than 10 Ohm). 
All the Inverters have an internal Input EMC filtering stadium, but is available also an 
additional EMC Input filter (various types, contact the service) for bigger noise 
suppression with sensitive devices connected on the line. 

15 

With a long cable between  
Inverter and Motor sometimes 
the inverter stop the motor in 
Pick Current alarm  

The motor can have high pick voltage value caused by the high frequency of the PWM 
combined with the high capacitance to ground of the long cable: we suggest to use an 
additional inverter output filter for cable longer than 40 meters connecting it directly on 
the Inverter output. Available various types of output filters, contact the service to 
receive informations. 

16 

The Differential Circuit Breaker 
on the line sometimes switch off 
the inverter 

Check the Ground system resistance (must be less than 10 Ohm). 
Use only differential circuit breaker type A (specific for Inverters). 

17 

The Magneto-Thermal Circuit 
Breaker on the line switch off the 
inverter when the pump run at 
the maximum power 

All the inverters may have a high pick value of the sinusoidal caused by the harmonics 
(5

th

 , 7

th

 , 11

th, 

etc.)  and depending by the resistance of the line, but this condition 

donÕt increase the energy absorbing value depending by the area under this current 
curve. Only you need to use a  Magneto-Thermal Circuit Breaker with a higher Current 
value than the value that you can use for the direct pump controlled. Usually itÕs 
enough a switch one step higher than the switch useful for the simple motor  (see 
table of the Magneto-Thermal protection suggested on the handbook). 

Table 10: solution of the most common installing problems 

8.  GUARANTEE 

Under the current European low: guarantee of 2 years calculated from the date of delivery of prejudice further 
provisions of law or contract. 
To have service in guarantee, it must submit to the company providing the guarantee certificate completed. 
The  guarantee  is  excluded  or  interrupted  in  anticipation  if  the  damage  is  caused  to  the  following:  
External  influences,  non-professional  installation,  non-compliance  with  instructions,  interventions  by 
unauthorized locations, use of not original spare parts and normal wear. 

Summary of Contents for IMTP 2.2 M-RS

Page 1: ...Motor Pump Inverter Type IMTP 2 2 M RS ITTP 2 2 M RS ITTP 4 M W RS ITTP 5 5 M W RS ITTP 7 5 W RS ENG Operation and maintenance handbook...

Page 2: ...5 Electric connection to Line and Motor 7 5 6 Pressure transducer connection on different types 8 5 7 Connections on the electronic board 9 6 STARTING AND PROGRAMMING 12 6 1 First Inverter Using Self...

Page 3: ...0mA or 0 5V output The control logic works with an output of 5 or 15V switchable that supplies the pressure transducer MINIMUM FLOW WORKING PROTECTION to prevent a closed delivery working the control...

Page 4: ...ty regulations could endangers others and damage the devices which can lead to loss of warranty The results of the non observance of the security rules can be Malfunctioning of the system Danger to ot...

Page 5: ...to remove the paint from the contact surface It is necessary to avoid ground loop that is like an antenna for EMC emission Power supply must be admitted on working condition don t lift or carry the m...

Page 6: ...ic system Before working be certain all the circuit is without voltage also the connections voltage clear Disconnect the inverter from the power supply before working on electrical or mechanical parts...

Page 7: ...wo cables connectors from the logic board J1 26 poles e J2 4 poles for IMTP2 2 ITTP2 2 Figure 5 or J5 26 poles for ITTP4 7 5 Figure 8 Connect the 3 motor terminals U V W on the power board on IMTP2 2...

Page 8: ...nnectors for IMTP ITTP2 2 fig 5 and J9 for ITTP4 7 5 fig 8 if previously disconnected making sure they are firmly fixed don t forget the clamp on J9 for ITTP4 7 5 fig 8 Replace and close the box using...

Page 9: ...9 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG 5 7 Connections on the electronic board Figure 5 Logic board of IMTP2 2 ITTP 2 2...

Page 10: ...10 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 6 Power board of IMTP 2 2 Figure 7 Power board of ITTP 2 2...

Page 11: ...11 IMTP 2 2 ITTP 2 2 4 5 5 7 5 ENG Figure 8 Logic board of ITTP 4 7 5 Figure 9 Power board of ITTP 4 7 5...

Page 12: ...pump is fully of water and close completely the outlet of the pump Pressing START for the Self Regulation Check for the registration of the curve of the pump for the regulation of the stop for closed...

Page 13: ...after the variation press ENTER Decrease the reference pressure during functioning ESC To exit to the function and automatically saving START Pump start STOP Pump stop If pressed with the key during...

Page 14: ...iangle see 5 3 Set the rotation direction 0 1 Default 0 Regulation of the minimum flow power for the motor stop in closed output condition Regulation of the dry working power stop default 80 Pump data...

Page 15: ...flow stop Default 12 second 15 second for ITTP4 7 5 4 Re start delay time after minimum flow stop Default 1 second 5 Dry working stop delay time for pump filling Default 40 seconds 6 When cos go down...

Page 16: ...faulty current control Automatic re start final stop after 10 consecutive events 13 Input Voltage under limit Input voltage under the minimum working limit Automatic re start final stop after 10 cons...

Page 17: ...output power to the motor then stop the motor and the inverter show Over Temperature IGBT alarm Inverter Temperature alarm Temperature of the electronic board of the inverter is too high and the inve...

Page 18: ...at pump haven t any defect fault seal impellers etc that can cause a big power absorbing also without water in dry condition 13 A group of two or more inverters cannot communicate between each other i...

Page 19: ...ctives and to national law following the technical standards Machines 98 37 CE Low Voltage 73 23 CE e successive modifiche and subsequent amendments IEC EN 61000 6 1 CEI EN 61000 6 4 ETSI EN 301 489 1...

Page 20: ...na Ind Esmoriz Sector C 8 36 13 86 O GPS OLIJU Manufacturing 40 57 27 11 N PORTUGAL PORTUGAL 4520 475 Rio Me o Zona Industrial de Rio Me o Avenida Santiago N 43 40 57 37 20 N 8 35 50 10 O GPS OLIJU Co...

Reviews: