8
– Particular specifications
41
Caution: when the measurement is above or equal to 100 % LEL,
the measurement controller records that the scale has been
exceeded; the channel switches to alarm and fault mode. The user is
responsible for manually rearming these settings, following the
safety regulations applicable at their site. Rearming can be
accomplished by restarting the controller or through a maintenance
operation.
Configuration transfer curve 0 to 30.0 % oxygen
The following curve demonstrates the controller response in terms of values
measured and treatment of faults, as a function of the value of the input
current delivered by the detector. In the case that the user connects a non -
Oldham
brand detector to the
MX 32
controller, the user must ensure that the
transfer curve is compatible with the input characteristics for the controller, so
that the information delivered by the detector will be properly interpreted. In
addition, the controller must provide sufficient supply voltage, taking into
account voltage drops in the cables.
Figure 11: Configuration transfer curve 0 to 30 % oxygen
Power supply and resistance characteristics
■
Maximum current available between terminals 2 and 3: 250 mA
under 19 V.
■
Maximum voltage without load between terminals 2 and 3: 30 V.
■
Resistance (outside of the intrinsic safety barrier) between terminals
1 and 2: 47 ohm.
Markings:
OLDHAM Arras
0080
II (1) (2) G
INERIS 04ATEX0064
Display in %
oxygen volume
Fault
Fault
Signal delivered by
the detector
Summary of Contents for MX 32
Page 36: ...32 MX 32 Instruction Manual...
Page 39: ...6 Declaration of Conformity 35 Chapter 6 Technical specifications...
Page 40: ...36 MX 32 Instruction Manual...
Page 46: ...42 MX 32 Instruction Manual...
Page 47: ......